UST500 CONTROL BOARD
06MC0074@00B0100
14/04/2010
29
Table B – analogue input logical meaning & parameter values CF12…CF15
Analogue input AI
Analogue input AI5 on
remote keyboard
Value
Description
AI1 AI2 AI3 AI4
AI5
0
Probe disabled
AI1 AI2 AI3 AI4
AI5
1
Internal exchanger water/air inlet temperature
AI1 AI2 AI3 AI4
AI5
2
Internal exchanger water/air outlet temperature
AI1 AI2 AI3 AI4
AI5
3
External exchanger temperature
AI1 AI2 AI3 AI4
AI5
4
External exchanger inlet water temperature
AI1 AI2 AI3 AI4
AI5
5
External exchanger outlet water temperature
AI1 AI2 AI3 AI4
AI5
6
External temperature
AI3 AI4
//
7
High pressure input
AI3 AI4
//
8
Low pressure input
AI3 AI4
//
9
Dynamic setpoint input
AI3 AI4
//
10
External exchanger pressure
AI3 AI4
//
11
Internal exchanger pressure
N.B: // indicates that value is not present
Configuration of digital inputs
The no voltage digital inputs referred to below as DI1…DI5 are 5 in total.
These can be added to by AI1…AI4 if the latter are configured as digital inputs (via parameters CF23…26 respectively).
A total of 8 digital inputs is thus available.
Study the following tables:
Table A – parameter association - configuration of digital inputs
Parameter
Description
Value
Description
Notes
CF16
Configuration of digital input DI1
-32…+32
See table B
CF17
Configuration of digital input DI2
-32…+32
See table B
CF18
Configuration of digital input DI3
-32…+32
See table B
CF19
Configuration of digital input DI4
-32…+32
See table B
CF20
Configuration of digital input DI5
-32…+32
See table B
CF23
Configuration of analogue input AI1
if configured as a digital input
-32…+32
See table B
Set to 0 if AI1
is NOT
configured as
a DI
CF24
Configuration of analogue input AI2
if configured as a digital input
-32…+32
See table B
Set to 0 if AI2
is NOT
configured as
a DI
CF25
Configuration of analogue input AI3
if configured as a digital input
-32…+32
See table B
Set to 0 if AI3
is NOT
configured as
a DI
CF26
Configuration of analogue input AI4
if configured as a digital input
-32…+32
See table B
Set to 0 if AI4
is NOT
configured as
a DI
Digital inputs