UST500 CONTROL BOARD
06MC0074@00B0100
14/04/2010
63
Antifreeze parameters with heat pump (folder PAr/AF)
Antifreeze parameters can be viewed and configured in folder AF (see User Interface and Parameters chapters).
The function is always active in any machine operating state, i.e. cooling, heating and standby.
The antifreeze function with water pump and heat pump is enabled
•
via parameter (AF00 - Enable heat pump function in antifreeze = 1)
The Heating LED flashes when this function is active.
For the antifreeze function, this function uses both the water pump and the heat pump.
Parameter
Description
Value
0
1
AF00
Enable heat pump operation in antifreeze
Heat pump disabled Heat pump enabled
Enable water pump / heat pump
•
The water pump activates (°) if the temperature read by the temperature control probe in COOL < AF01 water pump regulator
setpoint for heat pump function in antifreeze
•
The heat pump activates when the temperature control probe is adjusted in HEAT mode if the temperature read by the temperature
control probe in COOL mode < AF02 heat pump regulator setpoint in antifreeze
Disable water pump / heat pump
•
The water pump and heat pump will only disable if the temperature read by the temperature control probe in COOL mode exceeds
AF03 -Block heat pump setpoint in antifreeze
(°) water pump / heat pump will be activated if they were previously off; if they were on, they will stay on
Power
regulation probe
Heat Pump
ON
Water Pump
ON
AF03
AF01
AF02