UST500 CONTROL BOARD
32 06MC0074@00B0100
14/04/2010
Table B – Analogue Outputs – Configuration parameters
Output
Parameter
Description
Values
Notes
TC1
Only on
models
where this
is provided.
CF33
Enabling analogue output TC1
0= Output configured as ‘digital’
1= Output configured as triac
(proportional)
If=1
see parameters
CF36 – CF39 – CF42
CF36
Phase shift analogue output TC1
0…90
Has a meaning if
CF33=1
phase shift values to
pilot Triac with cut-off in
the event of inductive
loads.
CF39
Analogue output TC1 pulse length
5…40 units
(347…2776
µ
s)
Has a meaning if
CF33=1
pulse length to pilot
Triac
(1 unit = 69.4 µs).
CF42
Configuration of analogue output TC1
-13…+13 if digital (see polarity)
14…15 if proportional
See table entitled
Configuration of
analogue output
AO1
CF34
Enabling analogue output AO1
0= Output configured as ‘digital’
1= Output configured as Triac
(for pulse pilot)
If=1 see parameters
CF37 – CF40 - CF43
CF37
Phase shift analogue output AO1
0…90
Active if CF34=1
CF40
Analogue output AO1pulse length
5…40 units
(347…2776
µ
s)
Active if CF34=1
(1 unit = 69.4 µs).
CF43
Configuration of analogue output AO1
-13…+13 if digital (see polarity)
14…15 if proportional
See table entitled
Configuration of
analogue output
AO2
Only on
models
where this
is provided.
CF35
Enabling analogue output AO2
0= Output configured as ‘digital’
1= Output configured as Triac
(for pulse pilot)
If=1 see parameters
CF38 – CF41 - CF44
CF38
Phase shift analogue output AO2
0…90
Active if CF35=1
CF41
Analogue output AO2 pulse length
5…40 units
(347…2776
µ
s)
Active if CF35=1
(1 unit = 69.4 µs).
CF44
Configuration of analogue output AO2
-13…+13 if digital (see polarity)
14…15 if proportional
See table C
entitled Configuration of
analogue output
Output
Parameter
Description
Values
Notes
AO3
Only on
models
where this
is provided
CF27
Type of output analogue AO3
0=0-10V analogue output - voltage
1=4-20mA Analogue output - current
2=0-20mA Analogue output - current
See table entitled
Configuration of
analogue output
CF30
Configuration
Analogue output AO3
-13…+13 if digital (see polarity)
14…15 if proportional
Modulated piloting or
on/off via 10V external
relay
Note:
•
Parameters
CF37 CF38 CF40 CF41 have a meaning only if the outputs have been configured as Triac outputs (proportional).
•
Range CF39/CF40/CF41: 5…40 units or 347…2776 µs (1 unit = 69.4 µs).
Parameters CF37- CF42 – CF43 – CF44 see table C
Indicate the logical meaning of Triac analogue outputs.
The following can be piloted:
•
loads with output modulation (values from 14 to 16) or
•
loads with on/off type switching using
o
the
Triac as switch (TC1 AO1 AO2)
o
the output as switch 0-10V (AO3)
Analogue output
TC1 - AO1 AO2 :
Configuration
table
Low voltage
(SELV) analogue
output AO3:
Configuration
table