CONTROLLO UST500
84 06MC0074@00B0100
14/04/2010
External exchanger heater switch on setpoint for antifreeze
To modify the external exchanger switch on setpoint for antifreeze
Maximum external exchanger heater regulator setpoint for antifreeze
To modify the maximum setpoint of the external exchanger heater regulator for antifreeze.
Minimum external exchanger heater regulator setpoint for antifreeze
To modify the minimum setpoint of the external exchanger heater regulator for antifreeze.
External exchanger heater regulator hysteresis for antifreeze
To modify the regulator hysteresis of external exchanger heaters for antifreeze.
Auxiliary electric heater parameters (HA)
Enable auxiliary heater
To enable or disable auxiliary heater.
•
0 = Heaters disabled
•
1 = Heaters enabled
Auxiliary heater regulator setpoint
To set the auxiliary heater regulator setpoint.
Auxiliary heater regulator hysteresis
To set the auxiliary heater regulator hysteresis.
External circuit pump parameters (PE)
Enable external circuit water pump.
To enable or disable the external circuit water pump.
•
0 = Pump disabled
•
1 = Pump enabled
Boiler parameters (br) -boiler
Enable boiler
To enable or disable the boiler.
•
0 = Boiler disabled
•
1 = Boiler enabled
Enable boiler in heating only
To enable or disable the boiler in heating only.
•
0 = Boiler in integrated use
•
1
=
Boiler in heating
Enable boiler digital dynamic differential
To enable the digital dynamic differential of the boiler.
•
0 = Proportional
•
1 = Fixed
Boiler dynamic differential setpoint
To modify the setpoint of the boiler dynamic differential.
Boiler dynamic differential proportional band
To modify the proportional band of the dynamic differential of the boiler.
Maximum boiler dynamic differential
To modify the maximum dynamic differential of the boiler.
Boiler regulator hysteresis
To modify the hysteresis of the boiler regulator (
Defrost parameters (dF)
Enable defrost function
To enable or disable the defrost function.
•
0 = Defrost disabled
•
1 = Defrost enabled
Enable interval count between defrosts setpoint
To modify the setpoint enabling the interval count between defrosts.
Defrost deactivation setpoint
To modify the defrost deactivation setpoint.
Cumulative interval between defrosts
To modify the overall time between defrosts.
Compressor-valve-compressor delay before start defrost
To modify the time between the compressor-valve-compressor delay and start of defrost.
Compressor-valve-compressor delay at end of defrost.
To modify the time between the compressor-valve-compressor delay and end of defrost.
Dripping time
To modify dripping time.
Maximum defrost time.
To modify maximum defrost time.
HE03
HE04
HE05
HE06
HA00
HA01
HA02
PE00
br00
br01
br02
br03
br04
br05
br06
dF00
dF01
dF02
dF03
dF04
dF05
dF06
dF07