UST500 CONTROL
06MC0074@00B0100
14/04/2010
85
Enable dynamic defrost differential
To enable or disable the dynamic defrost differential.
•
0 = Offset disabled
•
1 = Offset enabled
Maximum dynamic defrost differential
To modify the maximum defrost dynamic differential.
Defrost dynamic differential setpoint
To modify the the dynamic differential setpoint for defrost.
Dynamic defrost differential proportional band
To modify the proportional band of the dynamic defrost differential.
Select probe to enable interval count between defrosts
To select the probe to enable the interval count between defrosts.
•
0 = External exchanger temperature
•
1 = High pressure input
•
2 = Low pressure input
•
3 = Internal exchanger pressure
•
4 = External exchanger pressure
Select probe to end defrost
To select the probe to end defrost.
•
0 = External exchanger temperature
•
1 = High pressure input
•
2 = Low pressure input
•
3 = Internal exchanger pressure
•
4 = External exchanger pressure
Setpoint to clear cumulative time between defrosts
To modify the setpoint clearing the cumulative time between defrosts.
Dynamic setpoint parameters (dS)
Enable dynamic temperature controller differential
To enable or disable the dynamic temperature controller differential.
•
0 = Dynamic setpoint disabled
•
1 = Dynamic setpoint enabled
Temperature controller dynamic differential proportional band in Cool
Temperature controller dynamic differential proportional band in Heat
To modify the proportional band of the temperature controller dynamic differential in Cool/Heat mode.
Maximum temperature controller dynamic differential in Cool
Maximum temperature controller dynamic differential in Heat
To modify the maximum dynamic differential of the temperature controller in Cool/Heat mode.
Temperature controller dynamic differential setpoint in Cool
Temperature controller dynamic differential setpoint in Heat
To modify the dynamic differential setpoint of the temperature controller in Cool/Heat mode.
Enable temperature controller digital dynamic differential.
To enable the digital dynamic differential of the temperature controller.
•
0 = Proportional
•
1 = Fixed
Adaptive parameters (Ad)
Enable machine function without accumulation
To enable or disable machine function without accumulation.
•
0 = Accumulation disabled
•
1 = Accumulation enabled
Accumulation offset type
To select the type of accumulation offset.
•
0 = Setpoint
•
1 = Hysteresis
•
2 = Setpoint and hysteresis
Accumulation offset constant
To modify the accumulation offset constant.
Accumulation offset differential
To modify the accumulation differential offset.
Block accumulation offset setpoint in cooling mode
To modify the block accumulation offset setpoint in Cool mode.
Block accumulation offset setpoint in heating mode
To modify the block accumulation offset setpoint in Heat mode.
Compressor on time for accumulation offset/regression
To modify the compressor on time for accumulation offset and regression.
Reference compressor on time for accumulation offset
To modify the reference compressor on time for accumulation offset.
dF08
dF09
dF10
dF11
dF12
dF13
dF14
dS00
dS01
dS02
dS03
dS04
dS05
dS06
dS07
Ad00
Ad01
Ad02
Ad03
Ad04
Ad05
Ad06
Ad07