UST500 CONTROL
06MC0074@00B0100
14/04/2010
81
Internal circuit water pump on time for antilock
To modify the internal circuit water pump on time for antilock.
PI19 – PI20 – PI21 ANTIFREEZE with PUMP
Enable antifreeze function with internal circuit water pump
To enable or disable the antifreeze function with internal circuit water pump.
•
0 = Function disabled
•
1 = Function enabled
Internal circuit water pump regulator setpoint for antifreeze
To modify the internal circuit water pump regulator setpoint for antifreeze.
Internal circuit water pump regulator hysteresis for antifreeze
To modify the internal circuit water pump regulator hysteresis for antifreeze.
Enable internal circuit water pump on when antifreeze heaters active
Enables the switching on of the internal circuit water pump when the antifreeze heaters are active.
•
0 = Pump disabled
•
1 = Pump enabled
Fan speed hysteresis to modulate internal circuit water pump in Heat
To modify fan speed hysteresis for modulation of the internal circuit water pump in Heat mode.
Fan speed hysteresis to modulate internal circuit water pump in Cool
To modify fan speed hysteresis for modulation of the internal circuit water pump in Cool mode.
Recirculation fan parameters (FI)
Enable recirculation fan
Enables or disables the recirculation fan.
•
0 = fan disabled
•
1 = fan enabled
Select recirculation fan operation
To select the operating mode of the recirculation fan.
•
0 = Always on
•
1 = On request
Recirculation fan regulator hysteresis in Cool mode
To modify the recirculation fan regulator hysteresis in Cool mode.
Recirculation fan regulator hysteresis in Heat mode
To modify the recirculation fan regulator hysteresis in Heat mode.
Enable Hot Start function
Enables or disables the Hot Start function
•
0 = Hot start disabled
•
1 = Hot start enabled
Hot Start regulator setpoint
To modify the regulator setpoint of the Hot Start function.
Hot Start regulator hysteresis
To modify the Hot Start function regulator hysteresis.
Postventilation time in Heat mode
To modify postventilation time in Heat mode.
Time between compressor on and recirculation fan on
To modify the delay between switching on the compressor and switching on the recirculation fan.
Secondary (external) exchanger fan parameters (FE)
Enable external exchanger fan
To enable or disable the external exchanger.
•
0 = fan disabled
•
1 = fan enabled
Select external exchanger fan operating mode
To select the operating mode of the external exchanger fan.
•
0 = ON/OFF
•
1 = Proportional
If FE01= 1 see parameters CF27-30 / CF33…CF44
External exchanger fan pick-up time
To vary the pick up time of the external exchanger fan.
Enable external exchanger fan on with compressor off
To enable or disable the switching on of the external exchanger fan when the compressor is off.
•
0 = Fan off with compressor OFF
•
1 = Fan on with compressor OFF
Bypass time for external exchanger fan cut-off
To modify the bypass time of the external exchanger fan cut-off.
External exchanger fan preventilation time in Cool
To modify the external exchanger fan preventilation time in Cool mode.
PI18
PI19
PI20
PI21
PI22
PI23
PI24
FI00
FI01
FI02
FI03
FI04
FI05
FI06
FI07
FI08
FE00
FE01
FE02
FE03
FE04
FE05