UST500 CONTROL BOARD
56 06MC0074@00B0100
14/04/2010
Auxiliary electric heaters (folder PAr/HA)
Parameters for auxiliary heaters can be viewed and configured in folder HA: Auxiliary electric heater parameters (see User Interface and
Parameters chapters).
•
They are active only when the relative parameter enabling them HA00=1 (see table)
•
In Std-by the heaters can be enabled by configuring HA01 (see table)
•
The control probe is based on external temperature.
•
The setpoint can be set in parameter HA01
Parameter
Description
Value
0
1
HA00
Enable auxiliary heaters Heaters
disabled
Heaters enabled
HA01
Enable auxiliary heater regulator
Heaters disabled
Heaters enabled
HA02
Auxiliary heater regulator hysteresis
Auxiliary heaters
Regulation is performed as shown in the figure:
HE01
Auxiliary heaters switch on setpoint
HE02
Auxiliary heater regulator hysteresis
Ext. temp
External temperature
Heaters
Heater state
OFF
Heaters
Ext. Temp
HA02
ON
HA01