UST500 CONTROL
06MC0074@00B0100
14/04/2010
83
Electric heater parameters (HI)
Enable internal exchanger heaters for antifreeze
To enable or disable internal exchanger heaters for antifreeze.
•
0 = Heaters disabled
•
1 = Heaters enabled
Enable internal exchanger heater regulator in standby for antifreeze
To enable or disable internal exchanger heaters in standby for antifreeze.
•
0 = Heaters disabled
•
1 = Heaters enabled
Enable integrated use of internal exchanger heaters
To enable or disable integrated use of internal exchanger heaters.
•
0 = Heaters disabled
•
1 = Heaters enabled
Enable force heaters on during defrost.
To enable or disable force heaters on during defrost.
•
0 = Heaters enabled (ON) when requested by temperature controller (antifreeze or integrated use)
•
1 = Heaters always enabled ON during defrost
See defrost parameters – folder dF
Number of internal exchanger heaters
To modify the number of internal exchanger heaters.
•
1 = 1 heater enabled
•
2 = 2 heaters enabled
Select probe to regulate internal exchanger heaters during antifreeze
To select the probe for regulation of internal exchanger heaters during antifreeze.
•
0 = Internal exchanger water/air inlet temperature
•
1 = Internal exchanger water/air outlet temperature
Internal exchanger heater regulator setpoint for antifreeze
To modify the internal exchanger heater regulator setpoint for antifreeze
Maximum internal exchanger heater regulator setpoint for antifreeze
To modify the maximum setpoint of the internal exchanger heater regulator for antifreeze.
Minimum internal exchanger heater regulator setpoint for antifreeze
To modify the minimum setpoint of the internal exchanger heater regulator for antifreeze.
Internal exchanger heater regulator hysteresis for antifreeze
To modify the hysteresis of the internal exchanger heater regulator for antifreeze.
Internal exchanger heater dynamic differential setpoint in integrated use
To modify the dynamic differential setpoint of the internal exchanger heaters in integrated use.
Maximum dynamic differential internal exchanger heaters in integrated use
To modify the maximum dynamic differential of the internal exchanger heaters in integrated use.
Internal exchanger heater dynamic differential proportional band in integrated use
To modify the proportional band of the dynamic differential of the internal exchanger heaters in integrated use.
Internal exchanger heater regulator hysteresis in integrated use
To modify the hysteresis of the internal exchanger heaters in integrated use.
Enable digital dynamic differential of internal exchanger heaters in integrated use
To enable the digital dynamic differential of the internal exchanger heaters in integrated use
•
0 = Proportional differential
•
1 = Fixed differential
Differential setpoint internal exchanger heater 2 on in integrated use
To modify the differential setpoint to switch on internal exchanger heater 2 in integrated use
External exchanger electric heater parameters (HE)
Enable external exchanger heaters for antifreeze
To enable or disable external exchanger heaters for antifreeze
•
0 = Heaters disabled
•
1 = Heaters enabled
Enable external exchanger heater regulator in standby for antifreeze
To enable or disable external exchanger heaters in standby for antifreeze.
•
0 = Heaters disabled
•
1 = Heaters enabled
Select probe to regulate external exchanger heaters during antifreeze
To select the probe to control the external exchanger heaters during antifreeze.
•
0 = External exchanger water inlet temperature
•
1 = External exchanger outlet water temperature
HI00
HI01
HI02
HI03
HI04
HI05
HI06
HI07
HI08
HI09
HI10
HI11
HI12
HI13
HI14
HI15
HE00
HE01
HE02