UST500 CONTROL BOARD
36 06MC0074@00B0100
14/04/2010
<IMG INF O>
56,4
29,75
1
2
51
-28, 35
-1
Proportional temperature control in HEAT mode (HEAT PUMP)
The compressor is controlled by an analogue input and by the Heating setpoint.
Heating setpoint: this is the reference setpoint when the device works in heat mode.
N.B.: temperature control is enabled in HEAT mode only if: tr01 (enable heat pump) = 1 (heat pump present)
See also Block Heat Pump
Probe AIn used in temperature control can be selected in parameter tr03:
N.B: Always set tr13> tr11
Power
power
*Step 1
Step 1
*Step 2
Step 2
*Only for machines with two compressors or partialized compressor.
AIn temp.
temperature read by the probe selected for temperature control in Heat.
A compressor will always be off if:
•
It is not associated with a relay (power output)
•
Compressor block active (see alarm table)
•
Safety timing is in progress
•
The boiler is active
•
A time delay is active between pump on and compressor on (safety timings)
•
Preventilation is in progress in cooling mode
•
UST500 is on standby or off
•
CF12…15 = 0 (probe absent)
Proportional
diagram in HEAT
<IMG INF O>