CONTROLLO UST500
76 06MC0074@00B0100
14/04/2010
Configuration of analogue output AO1
Configures analogue output AO1 – se table
0
Output disabled
9
External exchanger electric heater
1
Compressor 1
10
Auxiliary electric heater
2
Output step 2
11
External exchanger fan
3
Internal circuit water pump
12
Recirculation fan
4
External circuit water pump
13
Alarm
5
Reversing valve
14
Proportional external exchanger fan
6
Boiler
15
Not permitted
7
Internal exchanger electric heater 1
16
Modulating pump circuit
8
Internal exchanger electric heater 2
Configuration of analogue output AO2
Configures analogue output AO2 – same as CF43
Configuration of digital output DO1
Configures digital output DO1 – see table
0
Output disabled
7
Internal exchanger electric heater 1
1
Compressor 1
8
Internal exchanger electric heater 2
2
Power step
9
External exchanger electric heater
3
Internal circuit water pump
10
Auxiliary electric heater
4
External circuit water pump
11
External exchanger fan
5
Reversing valve
12
Recirculation fan
6
Boiler
13
Alarm
Configuration of digital output DO2
Configures digital output DO2 – same as CF45
Configuration of digital output DO3
Configures digital output DO3 – same as CF45
Configuration of digital output DO4
Configures digital output DO4 – same as CF45
Configuration of digital output DO5
Configures digital output DO5 – same as CF45
Configuration of digital output DO6 - Visible only in models ST551/C, ST552/C, ST553/C
Configures digital output DO6 – same as CF45
Configuration of digital output AO1
Configures digital output AO1 – same as CF45
Configuration of digital output AO2
Configures digital output AO2 – same as CF45
Select COM1 (TTL) protocol
Configures the selection of COM1 (TTL) communication channel protocol.
•
0 = Uniflair SpA
•
1 = Modbus
If CF54=0, the following CF55/CF56 parameters should be configured:
Uniflair SpA protocol controller address
Allows you to modify the Uniflair SpA protocol controller address.
Uniflair SpA protocol controller family
Allows you to modify the Uniflair SpA protocol controller family.
CF55= device index in family (values from 0 to 14)
CF56 = device family (values from 0 to 14)
The two values CF55 and CF56 represent the network address of the device, which is indicated in the following format
“FF.DD” (where FF=CF56 and DD=CF55).
If CF54=1, the following parameters should be configured: CF63/CF64/CF65
Modbus protocol controller address
To modify the Modbus protocol controller address.
Values from 1 to 255. N.B: 0 (zero) is not included.
Modbus protocol Baudrate
To modify the Modbus protocol baud rate.
•
0=1200
baud
•
1=2400
baud
•
2=4800
baud
•
3=9600
baud
•
4=19200
baud
•
5=38400 baud (maximum speed, to be set using
VarManager
software)
•
6=58600
baud
•
7=115200
baud
Modbus protocol parity
Modbus parity
•
0=
STX
•
1=
EVEN
•
2=
NONE
•
3=
ODD
Client code 1
Client code 2
Parameters for exclusive use by client/user. The client can assign these parameters values that e.g.
identify the type and/or model of the system, and its configuration etc.. Values from 0 to 255
CF43
CF44
CF45
CF46
CF47
CF48
CF49
CF50
CF51
CF52
CF54
CF55
CF56
CF63
CF64
CF65
CF66
CF67