UST500 CONTROL
06MC0074@00B0100
14/04/2010
75
Configuration of digital input DI2
To configure digital input DI2 – same as CF16
Configuration of digital input DI3
To configure digital input DI2 – same as CF16
Configuration of digital input DI4
To configure digital input DI4 – same as CF16
Configuration of digital input DI5
To configure digital input DI5 – same as CF16
Configuration of analogue input AI1 when configured as digital input
To configure analogue input AI1 when configured as digital input – same as CF16
Please Note: set to ‘0’ if AI1 is not configured as digital input
Configuration of analogue input AI2 when configured as digital input
To configure analogue input AI2 when configured as digital input – same as CF16
Please Note: set to ‘0’ if AI2 is not configured as digital input
Configuration of analogue input AI3 when configured as digital input
To configure analogue input AI3 when configured as digital input – same as CF16
Please Note: set to ‘0’ if AI3 is not configured as digital input
Configuration of analogue input AI4 when configured as digital input
To configure analogue input AI4 when configured as digital input – same as CF16
Please Note: set to ‘0’ if AI4 is not configured as digital input
Type of analogue output AO3 - Visible only in models ST544/C, ST553/C
It's analogue output AO3
•
0 = 0-10V
•
1 = 4-20mA
•
2 = 0-20mA
Configuration of analogue output AO3 - Visible only in models ST544/C, ST553/C
To configure analogue output AO3 – se table
0
Output disabled
±9
External exchanger electric heater
±1
Compressor 1
±10
Auxiliary electric heater
±2
Output step 2
±11
External exchanger fan
±3
Internal circuit water pump
±12
Recirculation fan
±4
External circuit water pump
±13
Alarm
±5
Reversing valve
±14
Proportional external exchanger fan
±6
Boiler ±15
Not permitted
±7
Internal exchanger electric heater 1
±16
Internal circuit modulating pump
±8
Internal exchanger electric heater 2
For visibility of parameters CF33 – CF44 See table at the beginning of this chapter.
Enabling analogue output TC1
Enables analogue output TC1
•
0 = Output configured as digital
•
1 = Output configured as triac
Enable analogue output AO1
Enables analogue output AO1
•
0 = Output configured as digital – see CF51
•
1 = Output configured as triac – see CF37 - CF40 - CF43
Enabling analogue output AO2
Enables analogue output AO2
•
0 = Output configured as digital – see CF52
•
1 = Output configured as triac – see CF38 - CF41 - CF44
Phase shift analogue output TC1
To enable phase shift of analogue output TC1
Phase shift analogue output AO1
To enable phase shift of analogue output AO1
Phase shift analogue output AO2
To enable phase shift of analogue output AO2
Analogue output TC1 pulse length
Configures analogue output pulse
Analogue output AO1pulse length
Configures analogue output AO1 pulse
Analogue output AO2 pulse length
Configures analogue output AO2 pulse
Configuration of analogue output TC1
Configures analogue output TC1
CF17
CF18
CF19
CF20
CF23
CF24
CF25
CF26
CF27
CF30
CF33
CF34
CF35
CF36
CF37
CF38
CF39
CF40
CF41
CF42
Содержание UST500