55
ANSI/IEEE C37.90.1 (SOW)
1-Phase power lines L-N coupling, 1 MHz, 2500 V
1-Phase power lines L-PE coupling, 1 MHz, 2500 V
1-Phase power lines LN-PE coupling, 1 MHz, 2500 V
1-Phase power lines N-PE coupling, 1 MHz, 2500 V
IEC TS 61000-6-5 (SOW)
1-Phase power lines L-N coupling, 1 MHz, 500/1000/2500 V
1-Phase power lines L-PE coupling, 1 MHz, 500/1000/2500 V
1-Phase power lines LN-PE coupling, 1 MHz, 500/1000/2500 V
1-Phase power lines N-PE coupling, 1 MHz, 500/1000/2500 V
IEC 61850-3 (SOW)
1-Phase power lines L-N coupling, 1 MHz, 2500 V
1-Phase power lines L-PE coupling, 1 MHz, 2500 V
1-Phase power lines LN-PE coupling, 1 MHz, 2500 V
1-Phase power lines N-PE coupling, 1 MHz, 2500 V
IEC 60255-26 (formerly IEC 60255-22-1) (SOW)
1-Phase power lines L-N coupling, 1 MHz, 1000/2500 V
1-Phase power lines L-PE coupling, 1 MHz, 1000/2500 V
1-Phase power lines LN-PE coupling, 1 MHz, 1000/2500 V
1-Phase power lines N-PE coupling, 1 MHz, 1000/2500 V
IEC 62052-11 (SOW)
1-Phase power lines L-N coupling, 100 kHz/1 MHz, 1000 V
1-Phase power lines L-PE coupling, 100 kHz/1 MHz, 2500 V
1-Phase power lines LN-PE coupling, 100 kHz/1 MHz, 2500 V
1-Phase power lines N-PE coupling, 100 kHz/1 MHz, 2500 V