Base setup
7.1
Jumper for the input signal
The internal connectors are factory set for input
“
E1
”
in the position for a 0 - 10 V input signal and for input
“
E2
”
for a
temperature sensor
“
TF.
”
.
On sensors with different signals, the internal connector must be set to the correct position.
Attention
–
this must be done when the power is disconnected. Observe safety information! When using
“
sensors from
other manufacturers
”
, the connector must be adjusted according to the signal. The measuring range is adjusted in the
basic settings for the operating mode.
E1 Analog In (factory setting 0 - 10 V)
A
E1
GND
0-10 V
10 k
0 - 10 V
TF..
24V
E1
GND
DSG 0 - 10 V
YE
DSG..
(0 - 10 V)
WH
BN
24V
E1
GND
MAL 0 - 10 V
3
MAL1/10
(0 - 10 V)
2
1
3
1
BN
GN
MBG..-I
24V
E1
MBG..
(4 - 20 mA)
E1
GND
TF..
03.02.2012
v_stecker_e1.vsd
E1.2
E1.1
0 - 10 V
E1.2
E1.1
0 - 10 V
E1.2
E1.1
0 - 10 V
E1.2
E1.1
4 - 20 mA
(0 - 20 mA)
E1.2
E1.1
TF.. (KTY)
E2 Analog In for operating modes with
2 sensors (factory setting TF..)
22.01.2008
v_stecker_e2.vsd
TF..
3
1
BN
GN
MBG..-I
24V
E2
MBG..
(4 - 20 mA)
E2
GND
TF..
E2.2
E2.1
4 - 20 mA
(0 - 20 mA)
E2.2
E2.1
TF.. (KTY)
7.1.1
External Setpoint / External speed setting in manual operation
External Setpoint or external manual operation is possible by 0 - 10 V (0 - 20 mA, 4 - 20 mA) Signal at terminals
“
E2
”
and
“
GND
”
. Place internal Jumper
“
E2.1
”
and
“
E2.2
”
for
“
E2 Analog In
”
in correct position.
“
E2
”
Con
fi
guration in base setup. For
Potentiometer Analog Out1 (terminal
“
A
”
) program to function
|
1A
|
=
“
+10 V
”
(like factory setting
IO Setup). If a second
sensor is connected at input 2, external Setpoint or speed setting in manual operation is possible with additional modul
“
Z-
Modul-B
”
(input E3
IO Setup).
E2 Analog In = 0 - 10 V
A
E2
GND
0-10 V
Analog In 2
02.12.2009
v_extern_stecker_v.vsd
E2.2
E2.1
10
k
E2 Analog In = 0 - 20 mA / 4 - 20 mA
E2.2
E2.1
Analog In 2
24.01.2008
v_extern_stecker_a.vsd
External Setpoint
via external signal instead of
“
Setpoint 1
”
. The
“
external Setpoint
”
function must be activated in base setup
|
1E
|
for
“
E2 function
”
. The active external Setpoint value is displayed in the
“
info
”
menu group.
External speed setting
in manual operation. The
“
external manual operation
”
function must be activated in the basic settings
|
2E
|
for
“
E2 function
”
. Switchover between settings on the device and external manual operation via the digital input (
IO
Setup:
“
Control / manual operation
”
|
7D
|
).
Operating Instructions
REPT6 / REPT10
Base setup
L-BAL-E081-GB 1237 Index 002
Part.-No. 00163316-GB