Offset 1 for alarm during exceeding
10
12
14
16
18
20
22
24
26
28
30
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
[min]
[
°C
]
ON
ON
ON
ON = 15°C + 5 K = 20 °C
OFF = 20°C - 2 K = 18 °C
1
6
.0
3
.2
0
0
7
v
_
re
la
is
_
k
u
e
h
le
n
_
1
0
k
_
p
o
s
_
o
ff
s
e
t.
v
s
d
Example: Setpoint 15.0
°
C, 5.0 K, Hysteresis 2.0 K
Offset 2 for alarm during undercutting
10
12
14
16
18
20
22
24
26
28
30
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
[min]
[
°C
]
ON
OFF = 15°C + 2 K = 17 °C
ON = 20°C - 5K = 15 °C
ON
1
6
.0
3
.2
0
0
7
v
_
re
la
is
_
h
e
iz
e
n
_
9
k
_
n
e
g
_
o
ff
s
e
t.
v
s
d
Example: Setpoint 15.0
°
C, Offset -5.0 K, Hysteresis 2.0 K
9.11
Motor Setup
9.11.1
Menu
“
Motorsetup
”
Motor Setup
Menu group Motor Setup
Parameter
Factory setting
User Setting
Rampup time
20 sec
Rampdown time
20 sec
Startvoltage
15 %
Suppression1
OFF
Range1 min.
- - - - -
Range1 max.
- - - - -
Suppression2
OFF
Range2 min.
- - - - -
Range2 max.
- - - - -
Suppression3
- - - - -
Range3 min.
OFF
Range3 max.
- - - - -
9.11.2
Setting for Rampup time and Rampdown time
By separate menus for Rampup time and Rampdown time an adjustment is possible to individual
system conditions.
This function is switched behind the actual controller function.
Rampup time
Rampup time
Time setting in which the automatic controller output from 0 % to 100 % rises.
Setting range: 0...250 sec.
Factory setting: 10 / 20 / 30 / 40 sec. (depending on device type)
Rampdown time
Rampdown time
Time setting in which the automatic controller output from 100 % to 0 % reduces.
Setting range: 0...250 sec.
Factory setting: 10 / 20 / 30 / 40 sec. (depending on device type)
Operating Instructions
REPT6 / REPT10
Programming
L-BAL-E081-GB 1237 Index 002
Part.-No. 00163316-GB
58/67