9.2
Temperature control
2.01
...
2.05
9.2.1
Basic setting
2.01
...
2.05
Base setup
Base setup
Mode
Mode
Mode selection e.g.
2.01
E1 Analog In
E1 Analog In
In all group 2 operating modes (2.01, 2.02, 2.03, ....)
“
E1 analogue In
”
factory set to
“
TF
”
(measuring range -20.5...+82.6
°
C).
Alternative selection Sensor:
“
MTG120V
”
Aktive sensor with 0 - 10 V output (
jumper for input signal) and proportional
measuring range: -10...+120
°
C.
Alternative selection signal: 0 - 10 V, 0 - 20 mA, 4 - 20 mA (
jumper for input signal)
accordingly inserted. The sensor measurement-range must be entered in order to
correctly display the actual value.
Example with a 0 - 10 V sensor and 0 - 100
°
C measurement range:
E1 Analog In = 0 - 10 V, E1 Min. = 0.0
°
C, E1 Max. = 100.0
°
C, E1 Decimally = 1, E1
Unit =
°
C
E1 Offset
E1 Offset
Sensor calibration with calibrated comparison device
E2 Function
E2 Function
(only for special applications)
•
Funktion
|
1E
|
= External Setpoint via external signal (0 - 10 V) instead of
“
Setpoint 1
”
.
–
For sensor type
“
E1 Analog In
”
=
“
TF
”
: 0 - 10 V
-20.5..+82.6
°
C.
–
For sensors with active signal: 0 - 10 V
0 - 100 % sensor measuring range.
•
Function
|
2E
|
= External manual operation via external signal (0 - 10 V). Switch
over between settings on the device and external manual operation via digital
input (
IO Setup).
•
Function
|
7E
|
Measurement value = Measurement value e.g. for limit indication,
display in Info menu
“
E2 Actual
”
.
Modes with two sensors
The function is automatically jointly programmed in operating modes using 2 sensors.
The second analog input is thus allocated and additional function allocations are not
possible.
•
2.04
E2 Function at
|
4E
|
preprogrammed = comparison value with control to
higher temperature. Alternative: average of 2 measuring points for this must be
reprogrammed on function
|
3E
|
preprogrammed sensor type
“
TF
”
.
•
2.05
E2 Function at
|
5E
|
preprogrammed = regulation on difference temper-
ature between sensor 1 and sensor 2. Preprogrammed sensor type
“
TF
”
.
Operating Instructions
REPT6 / REPT10
Programming
L-BAL-E081-GB 1237 Index 002
Part.-No. 00163316-GB
22/67