9.3
Pressure control airconditioning
4.01
...
4.03
9.3.1
Base setup
4.01
...
4.03
Base setup
Base setup
Mode
Mode
Mode selection e.g.
4.01
E1 Analog In
E1 Analog In
In all group 2 operating modes 4 (
4.01
,
4.02
,
4.03
, ....)
“
E1 Analog In
”
factory setting
“
DSG200
”
.
Selection sensor measuring range:
“
DSG 50
”
,
“
DSG100*
”
,
“
DSG200
”
,
“
DSG300*
”
,
“
DSG500
”
,
“
DSG1000
”
,
“
DSG2000
”
,
“
DSG4000
”
,
“
DSG6000
”
(* no standard type).
For sensors with 0 - 20 mA or 4 - 20 mA signal (
jumper for input signal), select
measuring range
“
DSG50
”
...
“
DSG6000
”
.
For not preprogrammed measuring range the sensor measurement range must be
entered in order to display the actual value correctly.
Example with a 0 - 10 V sensor and 0 - 400 Pa measurement range (proportional
output signal):
E1 Analog In = 0 - 10 V, E1 Min. = 0.0 Pa, E1 Max. = 400 Pa, E1 Dezimal = 1, E1 unit =
Pa
E1 Offset
E1 Offset
Sensor calibration with calibrated comparison device
E2 Function
E2 Function
(only for special applications)
•
External setpoint = Function
|
1E
|
by external signal (0 - 10 V) instead of
“
Setpoint 1
”
. 0 - 10 V
0 - 100 % sensor measuring range.
•
External manual operation via external signal (0 - 10 V) = Function
|
2E
|
Switch
over between settings on the device and external manual operation via digital
input (
IO Setup).
•
Measurement value = function
|
7E
|
e.g. for limit indication, display in Info menu
“
E2 Actual.
”
Modes
4.02
and
4.03
with two sensors
The function is automatically jointly programmed in operating modes using 2 sensors.
The second analog input is thus allocated and additional function allocations are not
possible.
For
4.02
E2 Function at
|
6E
|
preprogrammed = sensor for setpoint lowering. Preprog-
rammed sensor type
“
TF..
”
For
4.03
|
E2
|
Function at
|
6E
|
preprogrammed = sensor for setpoint lowering.
- preprogrammed sensor type
“
BUS
”
- measuring range -35.0...+65.0
°
C
In
“
IO Setup
”
:
For enable
“
ON
”
/
“
OFF
”
via Bus:
- D1 function =
|
1D
|
- D1 Busmode =
“
ON
”
For switch over setpoint 1 /2 via Bus:
- D2 function =
|
5D
|
,
- D2 Busmode =
“
ON
”
Operating Instructions
REPT6 / REPT10
Programming
L-BAL-E081-GB 1237 Index 002
Part.-No. 00163316-GB
29/67