9.3.2
Setting for operation modes
4.01
...
4.03
•
4.01
pressure control, setpoint in Pa
•
4.02
and
4.03
Pressure control for ventilation systems setpoint depending on outdoor temper-
ature
Setting
Setting
Setpoint1
Setpoint1
Setting range: in measuring range of sensor
Factory setting: 100 Pa
Setpoint2
Setpoint2
Setting
“
Setpoint 2
”
e.g. reduced value for night operation.
Switch over Setpoint 1/2 by external contact (as long as no allocation is carried out:
Display:
|
- - - - -
|
IO Setup).
Pband
Pband
Narrow control range = Short control times
Wide control range = Longer control times and more stable control
Setting range: in measuring range of sensor
Factory setting: 100 Pa
Min. Speed
Minimal Speed
Setting range: 0...100 %
Factory setting: 0 %
Max. Speed
Maximal Speed
Setting range: 100 %...
“
Min. Speed
”
Factory setting: 100 %
Manual mode
Manual mode
“
OFF
”
= automatic control as function of the set parameters (Factory setting)
“
ON
”
= automatic control without function, speed setting in menu
“
Speed manual
”
Speed man.
Speed Manual mode
Manual speed setting without in
fl
uence by the external signal.
Activation by menu
“
Manual mode
”
or external contact at digital input (
IO Setup).
Setting range: 0...100 %
Factory setting: 100 %
For information about deactivated regulation the adjusted value for manual speed is
indicated alternating with the actual value.
Operating Instructions
REPT6 / REPT10
Programming
L-BAL-E081-GB 1237 Index 002
Part.-No. 00163316-GB
30/67