9.8.11
Data on the total control deviation
The total control deviation is comprised of the sum of the control deviations for performance quantities
and work quantities combined and refers to the speci
fi
ed areas.
In direct reference to the acquired input and controlled variables, the maximum deviation to the target
value is <
±
5 %. By activating the menu-assisted adjustment, the total control deviation can be
reduced to a value of <
±
1 %.
For indirect reference of the acquired input value to the controlled variable, i.e., two physical variables
still need to be converted, the deviation can be reduced to <
±
5 % through adjustment.
In the case of an internal default value through the integrated or external terminal, the control deviation
remains at <
±
0.5%.
9.9
IO Setup
9.9.1
Menu overview
“
IO Setup
”
IO Setup
IO Setup
Parameter
Factory setting
User Setting
A Function
1A (6A**)
A / A2 Function
A min.
0.0 V
|
1A
|
Constant v10 V
A max.
10.0 V
|
2A
|
proportional level control
A Inverting
OFF
|
3A
|
proportional input E1
A2* Function
1A
|
4A
|
proportional input E2
A2* min.
0.0 V
|
5A
|
Group control
A2* max.
10.0 V
|
6A
|
only 2.03 Cooling function
A2 Inverting
OFF
|
7A
|
only 2.03 Heating function
D1 Function
OFF
D1 Inverting
- - - -
D1...D5 function
D1 Busmode
- - - -
|
1D
|
Enable ON / OFF
D2 Function
OFF
|
2D
|
External error
D2 Inverting
- - - -
|
3D
|
Limit ON / OFF
D2 Busmode
- - - -
|
4D
|
Switch over Signal E1/E2
D3* Function
OFF
|
5D
|
Setpoint1/2
D3* Inverting
- - - -
|
6D
|
Switch over: Intern/Extern
D4* Function
OFF
|
7D
|
Control / manual Intern
D4* Inverting
- - - - -
|
8D
|
Switch over: actual Val > Set = n+ / n-
D5* Function
OFF
|
10D
|
Reset
D5* Inverting
- - - -
|
11D
|
Setting Max. Speed ON / OFF
E1 Inverting
OFF
|
12D
|
Motorheating (not Acontrol)
E2 Inverting
- - - -
|
13D
|
Change over Rolling direction (only Fcontrol, Icon-
trol)
E3* Function
OFF
|
14D
|
“
Freeze
”
function modulation value
E3* Inverting
- - - -
E3 Function
K1 Function
1K (2K**)
|
1E
|
0 - 10 V external Setpoint
K1 Inverting
OFF
|
2E
|
External Manual mode
K2 Function
2K (9K**)
K1...K4 function
K2 Inverting
OFF
|
1K
|
Operating indication
K3* Function
OFF
|
2K
|
Fault indication
K3* Inverting
- - - -
|
3K
|
External alarm indication
K4* Function
OFF
|
4K
|
Limit modulation
K4* Inverting
- - - -
|
5K
|
Limit E1
Bus Address
247
|
6K
|
Limit E2
Addressing
OFF
|
7K
|
Setpoint Offset
Operating Instructions
REPT6 / REPT10
Programming
L-BAL-E081-GB 1237 Index 002
Part.-No. 00163316-GB
44/67