9.4
Volume control
5.01
and
5.02
9.4.1
Basic setting
5.01
and
5.02
Setting
Base setup
Base setup
Mode
Mode selection e.g.
5.01
E1 Analog In
E1 Analog In
In all group operating modes 5 (
5.01
and
5.02
)
“
E1 Analog In
”
factory setting
“
DSG200.
”
Selection sensor measuring range:
“
DSG 50
”
, *
“
DSG100
”
,
“
DSG200
”
, *
“
DSG300
”
,
“
DSG500
”
,
“
DSG1000
”
,
“
DSG2000
”
,
“
DSG4000
”
,
“
DSG6000
”
(* no standard type).
For sensors with 0 - 20 mA or 4 - 20 mA signal (
jumper for input signal), select
measuring range
“
DSG50
”
...
“
DSG6000
”
.
K Factor
K Factor
Input of the
“
K factor
”
dependent on the fan (inlet duct).
setting range: 0...7.000
Factory setting: 75
E1 Offset
E1 Offset
Sensor calibration with calibrated comparison device
E2 Function
E2 Function
(only for special applications)
•
External setpoint = Function
|
1E
|
by external signal (0 - 10 V) instead of
“
Setpoint 1
”
. 0 - 10 V
0 - 100 % setting range
•
External manual operation via external signal (0 - 10 V) = Function
|
2E
|
Switch
over between settings on the device and external manual operation via digital
input (
IO Setup).
•
Measurement value = function
|
7E
|
e.g. for limit indication, display in Info menu
“
E2 Actual
”
Modes
5.02
with two sensors
Modes with two sensors The function is automatically jointly programmed in operating
modes using 2 sensors. The second analog input is thus allocated and additional
function allocations are not possible. For
5.02
E2 Function at
|
6E
|
preprogrammed =
sensor for setpoint lowering. Pre-programmed sensor type
“
TF
”
.
9.4.2
Setting for operation modes
5.01
...
5.02
•
5.01
Volume control, Setpoint in m
3
/h
•
5.02
Volume control for ventilation systems setpoint depending on outdoor temperature.
Setting
Setting
Setpoint1
Setpoint1
Setpoint in m
3
/h (m
3
/s)
Setting range: depending on measuring range of sensor and
“
K factor
”
Factory setting: 530 m
3
/h
Setpoint2
Setpoint2
Setting
“
Setpoint 2
”
e.g. reduced value for night operation.
Switch over Setpoint 1/2 by external contact (as long as no allocation is carried out:
Display:
|
- - - - -
|
IO Setup).
Operating Instructions
REPT6 / REPT10
Programming
L-BAL-E081-GB 1237 Index 002
Part.-No. 00163316-GB
33/67