Pband
Pband
Narrow control range = Short control times
Wide control range = Longer control times and more stable control
Setting range: depending on measuring range of sensor and
“
K factor
”
Factory setting: 530 m
3
/h
Min. Speed
Minimal Speed
Setting range: 0...100 %
Factory setting: 0 %
Max. Speed
Maximal Speed
Setting range: 100 %...
“
Min. Speed
”
Factory setting: 100 %
Manual mode
Manual mode
“
OFF
”
= automatic control as function of the set parameters (Factory setting)
“
ON
”
= automatic control without function, speed setting in menu
“
Speed manual
”
Speed man.
Speed Manual mode
Manual speed setting without in
fl
uence by the external signal.
Activation by menu
“
Manual mode
”
or external contact at digital input (
IO Setup).
Setting range: 0...100 %
Factory setting: 100 %
For information about deactivated regulation the adjusted value for manual speed is
indicated alternating with the actual value.
Additional menu item for mode
5.02
with outside-temperature dependent target-setpoint
Outside-temperature dependent target-setpoint
Außentemperatur
P-min SA
[m
3
/h]
-15 °C
min. Temperatur
30 °C
T-Start
Sollwert 1
[m
3
/h]
Sollwert 2
[m
3
/h]
07.02.2007
v_sollwert_aussentemp_abhaengig_m3h.vsd
S1
Setpoint1
S2
Setpoint2
P-Min SA
Minimum air volume
T-min
Minimum temperature
T-Start
Setpoint reducing will start below this outside temperature
AT
Outdoor temperature
An outside temperature compensation can be
activated (sensor connection
“
E2
”
to
“
Analog In
2
”
) when being operated as a air volume regu-
lation device.
An optimal building climate, e.g., can be
achieved through this. Through this function,
the set and active Setpoint 1/2 is automatically
changed proportional to the measured outside
temperature (
Info:
“
Setpoint control
”
).
T-Band SA
T-Band SA
Temperature range in which the setpoint change continiously with outside temperature
T-Start SA
T-Start SA
Setpoint reducing will start below this outside temperature
P-Min SA
P-Min SA
Minimum pressure for very low outside temperature