9
Programming
9.1
Speed controller
1.01
9.1.1
Base setup
1.01
Base setup
Base setup
Mode
Mode
Factory setting Mode:
1.01
E1 Analog In
E1 Analog In
Selection: 0 - 20 mA, 4 - 20 mA, Bus (Inverting
IO Setup)
Factory setting: 0 - 10 V
E2 Function
E2 Function
(only for special applications)
Analog input 2
“
E2
”
factory set at
“
OFF
”
.
For operation with a second signal and switch over via
fl
oating contact set function for
“
E2
”
to
|
1E
|
(
IO Setup: function
|
4D
|
).
For operation with a second signal and automatic control at the higher level. Set
“
E2
”
Function to
|
4E
|
.
E2 Analog In
E2 Analog In
As long as no allocation has been carried out display:
|
- - - - -
|
Selection: 0 - 20 mA, 4 - 20 mA, Bus (Inverting
IO Setup)
Factory setting: 0 - 10 V
9.1.2
Setting for operation
1.01
Setting
Setting
Set Intern1
Set Intern1
Setting range Manual speed setting: 0...100 %
Factory setting: 80 %
Set Intern2
Set Intern2
Setting
“
Set Intern2
”
e.g. reduced value for night operation.
Switch over intern 1/2 by external contact (as long as no allocation is carried out:
Display:
|
- - - - -
|
IO Setup).
Min. Speed
Minimal Speed
Setting range: 0...100 %
Factory setting: 0 %
Max. Speed
Maximal Speed
Setting range: 100 % -
“
Min. Speed
”
Factory setting: 100 %
Set external1
Set external1
“
ON
”
(factory setting) = speed setting by external Signal
“
OFF
”
= Setting
“
Set Intern1
”
Operating Instructions
REPT6 / REPT10
Programming
L-BAL-E081-GB 1237 Index 002
Part.-No. 00163316-GB
20/67