15.05.2009
v_11d_max_drehzahl.vsd
Controller
24V
D1 D1
= 80 %
1
0
- - - - -
1
0
= 0 .. 100 %
1
1
Setting
“
Max. Speed
”
(depending on device type in: %, Hz, rpm)
•
“
D1 Inverting
”
=
“
OFF
”
:
“
Max. Speed
”
active at closed contact
•
“
D1 Inverting
”
=
“
ON
”
:
“
Max. Speed
”
active at opened contact
9.9.3.12
“
Freeze function
”
= maintain momentary modulation value, Function
|
14D
|
The device continues to work so long independently of the controller function with the momentary
value of the modulation and / or speed as activated over the digital input.
Freeze
Message indicated alternating with the active value
“
Freeze Function
”
Contact at digital input e.g.
“
Digital In 1
”
“
D1 Inverting
”
=
“
OFF
”
:
“
Freeze function
”
at closed contact activ
“
D1 Inverting
”
=
“
ON
”
:
“
Freeze function
”
at opened contact activ
9.9.4
Inverting analog inputs
“
E1
”
/
“
E2
”
After programming the signal or sensor type, an inversion of the inputs can be carried out.
E1 Inverting
Factory setting for Inverting inputs =
“
OFF
”
(if input activated) (signal: 0 - 10 V, 0 - 20
mA, 4 - 20 mA).
For activation using inverted default signals or sensors with inverted output signals
proportional to the measurement range, switch inverting to
“
ON
”
(Signal: 10 - 0 V, 20 - 0
mA, 20 - 4 mA).
E2 Inverting
Operating Instructions
REPT6 / REPT10
Programming
L-BAL-E081-GB 1237 Index 002
Part.-No. 00163316-GB
51/67