For modes as controller higher
2.01
7K
Setpoint Offset
Deviation between actual value and setpoint to high
8K
Group control
Switching on fans depending on modulation
For modes as temperature controller with additional functions
2.03
9K
Heating function
Switch ON point: temperature = Se/- Offset
Switch OFF point: Temperature around hysteresis over switch ON point
10K
Cooling function
Switch ON point: temperature = Se/- Offset
Switch OFF point: Temperature around hysteresis below switch ON point
14.05.2007
v_relais_k1_k2_pxet_5amp.vsd
14
12
11
24
22
21
K1
K2
Max. contact load 5A / 250 VAC
K1
1
= energized, terminals 12 - 14 bridged
0
= de-energized 11 - 12 bridged
K2
1
= energized, terminals 22 - 24 bridged
0
= de-energized 21 - 22 bridged
Function Controller status
K1/ K2
1 = energized
0 = de-energized
Inverting
OFF
ON
1K
Operation without fault, line supply okay
1
0
2K
Fault with indication by relay
0
1
3K
Ext. Fault at digital input for external fault
1
0
4K
Over or falling below limits for modulation
1
0
5K
over or falling below limits for input signal
“
E1
”
1
0
6K
over or falling below limits for input signal
“
E2
”
1
0
7K
setpoint deviation to high
1
0
8K
Activation of second group
1
0
9.9.6
Programming Add-on module type Z-Modul-B
Program the additional inputs and outputs likewise in
“
IO Setup
”
.
After connecting the module, the settings menus are automatically expanded to include the additional
inputs and outputs.
•
1 x analog input 0 - 10 V. For mode
1.01
without function, starting from
2.01
funktion
|
1E
|
or
|
2E
|
possible.
–
Function
|
1E
|
for external target value function.
–
Function
|
2E
|
for external manual operation.
•
1 x output 0 - 10 V (A2 / GND), Function programmable, e.g., for: Fixed voltage, proportional
level control, proportional input signal, group control, drive 2.
•
3x digital inputs (D3 / GND, D4 / GND, D5 / GND) function programmable, e.g.: Enable (ON /
OFF), external malfunction, output limitation, input 1/2, target value 1/2, internal/external preset,
controller / manual operation, control-function reversal (
“
heating
”
/
“
cooling
”
).
•
2 x relay outputs (
“
K3
”
and
“
K4
”
) Function programmable, e.g., for: Status signals, alarm
indications, external malfunctions at the digital input, level-control threshold, input signal thresh-
old, offset threshold (deviation between current and target value), group control.
Operating Instructions
REPT6 / REPT10
Programming
L-BAL-E081-GB 1237 Index 002
Part.-No. 00163316-GB
53/67