9.5
Air velocity control
6.01
9.5.1
Base setup
6.01
Base setup
Base setup
Mode
Mode
Mode selection
6.01
E1 Analog In
E1 Analog In
For mode
6.01
“
E1 Analog In
”
factory setting to
“
MAL1
”
Selection sensor measuring range: MAL1, MAL10
Alternative selection signal: 0 - 10 V, 0 - 20 mA, 4 - 20 mA (
jumper for input signal).
The sensor measurement range must be entered in order to display the actual value
correctly. Example with a 0 - 10 V sensor and 0 - 5 m/s measurement range (propor-
tional output signal).
E1 Analog In = 0 - 10 V, E1 Min. = 0.0 m/s, E1 Max. = 5.0 m/s, E1 Decimals = 1, E1
Unit = m/s
E1 Offset
Sensor calibration with calibrated comparison device
E2 Function
Function Analog Input 2
•
External setpoint = Function
|
1E
|
by external signal (0 - 10 V) instead of
“
Setpoint 1
”
. 0 - 10 V
0 - 100 % setting range
•
External manual operation via external signal (0 - 10 V) = Function
|
2E
|
Switch
over between settings on the device and external manual operation via digital
input (
IO Setup).
•
Measurement value = function
|
7E
|
e.g. for limit indication, display in Info menu
“
E2 Actual.
”
9.5.2
Settings for operation modes
6.01
Setting
Setting
Setpoint1
Setpoint1
Setting range: in measuring range of sensor
Factory setting: 0.50 m/s
Setpoint2
Setpoint2
Setting
“
Setpoint 2
”
e.g. reduced value for night operation.
Switch over Setpoint 1/2 by external contact (as long as no allocation is carried out:
Display:
|
- - - - -
|
IOSetup).
Pband
Pband
Narrow control range = Short control times
Wide control range = Longer control times and more stable control
Setting range: in measuring range of sensor
Factory setting: 0.50 m/s
Min. Speed
Minimal Speed
Setting range: 0...100 %
Factory setting: 0 %
Operating Instructions
REPT6 / REPT10
Programming
L-BAL-E081-GB 1237 Index 002
Part.-No. 00163316-GB