Display
STOP
for switch OFF
•
Controller
“
ON
”
for closed contact
(factory setting).
•
Controller
“
OFF
”
with opened con-
tact
When inverting in reverse i.e. equipment
“
OFF
”
with closed contact.
D1
D1
D1
D1
Digital IN 1
Digital IN 1
ON
OFF
10.05.2007
v_1d_freigabe_d1_d1.vsd
Contact at digital input e.g.
“
Digital In 1
”
Attention!
No disconnection when turned off (no isolation in accordance with VBG4
§
6)!
9.9.3.3
External fault Function
|
2D
|
Connecting an external alarm indication (via
fl
oating contact). The device continues to work un-
changed during an external indication to the digital input; the alarm symbol appears in the display.
This indication can be issued via the relay contacts (K1, K2) (
IO Setup function K1, K2).
Example for connecting an external alarm indication e.g. to digital input
“
Digital In 1
”
Controller
1~ S-ET..
3~ STDT..
TB
TB
TB
K1
D1
D1
10.05.2007
v_2d_externe_stoerung_set_stdt.vsd
1~ S-ET..
3~ STDT..
1~ S-ET..
3~ STDT..
•
Indication during closed contact (factory setting):
“
D1 Inverting
”
=
“
OFF
”
•
Indication during opened contact:
“
D1 Inverting
”
=
“
ON
”
Actual value
Alarm symbol for indication
“
External fault
”
9.9.3.4
Limit ON / OFF, Function
|
3D
|
The value for
“
Limit
”
adjusted in the Controller Setup, is activated over a digital input.
Contact e.g. at ditgital input
“
Digital In 1
”
(depending on device type at terminals
“
D1
”
-
“
D1
”
or
“
D1
”
-
“
24 V
”
).
For
“
D1
”
Inverting
“
OFF
”
, limitation active at closed contact.
Operating Instructions
REPT6 / REPT10
Programming
L-BAL-E081-GB 1237 Index 002
Part.-No. 00163316-GB
47/67