Additional menu item for mode
4.02
and
4.03
with outside-temperature dependent target-
setpoint.
Outside-temperature dependent target-setpoint
Außentemperatur
P-min SA
[Pa]
-15 °C
min. Temperatur
30 °C
T-Start
Sollwert 1
[Pa]
Sollwert 2
[Pa]
07.02.2007
v_sollwert_aussentemp_abhaengig_pa.vsd
S1
Setpoint1
S2
Setpoint2
P-Min SA
Minimum pressure
T-min
Minimum temperature
T-Start
Setpoint reducing will start below this outside temperature
AT
Outdoor temperature
An outside temperature compensation can be
activated (sensor connection
“
E2
”
=
“
Analog In
2
”
) when being operated as a pressure regula-
tion device.
An optimal building climate, e.g., can be
achieved through this. Through this function,
the set and active
“
Setpoint 1
”
or
“
Setpoint 2
”
is
automatically changed proportional to the
measured outside temperature (
Info:
“
Set-
point control
”
).
T-Band SA
T-Band SA
Temperature range in which the setpoint change continiously with outside temperature
T-Start SA
T-Start SA
Setpoint reducing will start below this outside temperature
P-Min SA
P-Min SA
Minimum pressure for very low outside temperature
Operating Instructions
REPT6 / REPT10
Programming
L-BAL-E081-GB 1237 Index 002
Part.-No. 00163316-GB
31/67