Controller
24V
D1 D1
1
0
n = 0 -100 %
1
n = 80 %
0
- - - - -
- - - - -
- - - - -
Se
E1
ES
E2
26.05.2010
v_7d_regelung_hand.vsd
3
2
1
1
Setting
“
Setpoint1
”
2
Setting
“
Setpoint2
”
3
Setting
“
Speed manual
”
(depending on device type in: %, Hz, rpm)
EH
Signal for Manual mode extern, E2 Function =
|
2E
|
Se
Sensor
•
“
D1 Inverting
”
=
“
OFF
”
Automatic
control at opened contact / manual
operation at closed contact.
•
“
D1 Inverting
”
=
“
ON
”
: Automatic control
at closed contact / manual operation at
opened contact.
9.9.3.9
Reverse action of control function (
2.01
), Function
|
8D
|
Switchover between: Increasing modulation during increasing actual-value and increasing modulation
during sinking actual-value.
The factory presets for the
“
Control function
”
are dependent on the selected mode of operation (
Controller Setup - reverse operation of the control function).
When switching over via a digital input, the device works with the opposite function than the one set
there!
Val>Set=n+
Settings in Controller Setup
9.9.3.10
Reset, Function
|
10D
|
Reset after motor fault by using an non-locking reset key. The unit switches off when interruption
between both
“
TB/TP
”
or
“
TK/PTC
”
terminals, the unit then remains switched off (
“
motor fault
”
see
motor protection). Re-starting after the drive has cooled down (terminals
“
TB/TP
”
- or
“
TK/PTC
”
bridged) by non-locking reset key possible.
Contact at digital input e.g.
“
Digital In 1
”
•
For
“
D1 Inverting
”
=
“
OFF
”
both
terminals
“
D1
”
-
“
D1
”
in normal operation
interrupted. Reset after fault by short
close.(For
“
Inverting
”
=
“
ON
”
reverse
function).
9.9.3.11
Setting Max. Speed ON / OFF function
|
11D
|
The value for
“
Max Speed
”
adjusted in menu
“
Settings
”
, is activated over a digital input. I.e. the unit
works independently of the controller function
fi
rm with this value.
Contact e.g. at ditgital input
“
Digital In 1
”
(depending on device type at terminals
“
D1
”
-
“
D1
”
or
“
D1
”
-
“
24 V
”
).
Operating Instructions
REPT6 / REPT10
Programming
L-BAL-E081-GB 1237 Index 002
Part.-No. 00163316-GB
50/67