Max. Speed
Maximal Speed
Setting range: 100 %...
“
Min. Speed
”
Factory setting: 100 %
Manual mode
Manual mode
“
OFF
”
= automatic control as function of the set parameters (Factory setting)
“
ON
”
= automatic control without function, speed setting in menu
“
Speed manual
”
Speed man.
Speed Manual mode
Manual speed setting without in
fl
uence by the external signal.
Activation by menu
“
Manual mode
”
or external contact at digital input (
IO Setup).
Setting range: 0...100 %
Factory setting: 100 %
For information about deactivated regulation the adjusted value for manual speed is
indicated alternating with the actual value.
9.5.3
Menu for air velocity control
6.01
Parameter
Factory setting
User Setting
Start
PIN input
- - - - -
Language
GB
Reset
OFF
Mode
6.01
Acontrol
1.14
Info
E1 Actual
0.45 m/s
E2 Actual
- - - - -
Setpoint1
0.50 m/s
Modulation
0 %
Msco
OFF
Setting
Setpoint1
0.50 m/s
Setpoint2
- - - - -
Pband
0.50 m/s
Min. Speed
0 %
Max. Speed
100 %
Manual mode
OFF
Speed man.
100 %
Events
Base setup
Mode
6.01
6.01
Air velocity control
E1 Analog In
0-1 MAL
E1 Min.
- - - - -
E1 Max.
- - - - -
E1 Decimals
- - - - -
E1 Unit
- - - - -
E2 Function
E1 Offset
0.0 m/s
|
1E
|
external Setpoint
E2 Function
OFF
E2 Analog In
- - - - -
|
2E
|
external manual mode
Operating Instructions
REPT6 / REPT10
Programming
L-BAL-E081-GB 1237 Index 002
Part.-No. 00163316-GB