9.2.4
Additional for mode
2.03
: Signal output 0 - 10 V
The 0 - 10 V output signal can, e.g., be used for triggering a shutter or heating.
Offset AnalogOut
Offset AnalogOut
The target value for this output is the target value (Setpoint) for the ventilation
“
offset
”
setting.
Adjustment: range +/- 10 K relative to the active Setpoint.
Example for triggering a shutter servomotor:
At factory setting
“
0 K
”
= synchronous operation.
The analog output is factory set to increasing activation during increasing temperature.
Reprogramming to
“
Heating function
”
, i.e., increasing modulation during decreasing
temperature is possible (
IO Setup).
Pband AnalogOut
Pband AnalogOut
Pband AnalogOut = separately adjustable range of control (P-band) for 0 - 10 V output
Setting range: 0...102.0 K
Factory setting: 2.0 K
Min. AnalogOut
Min. AnalogOut
Min. AnalogOut = Minimal output voltage
Setting range: 0...100 % = 0 - 10 V
Factory setting: 0 %
Max. AnalogOut
Max. AnalogOut
Max. AnalogOut = Maximal output voltage,
Setting range: 100...0 % = 10 - 0 V
Factory setting: 0.0 K
Example for signal out 0 - 10 V
(IO Setup:
“
A function
”
=
|
6A
|
)
Max. Analog Out
10 V
50 %
100 %
I
Min. Analog Out
Min. 0 %
Max. = 100 %
Min. 35 %
Max. = 85 %
20 °C
S
10 K
R
30 °C
09.05.2007
v_signal_ausgang_0_10_v.vsd
Example: Setpoint ventilation 25.0
°
C, Offset -5.0 K, Pband 10.0 K
S
Setpoint Venti/- Offset
R
Pband
I
Actual value
Operating Instructions
REPT6 / REPT10
Programming
L-BAL-E081-GB 1237 Index 002
Part.-No. 00163316-GB
25/67