8
Start-up
8.1
Prerequisites for commissioning
Attention!
1. You must mount and connect the device in accordance with the operating instructions.
2. Double check that all connections are correct.
3. The mains voltage must match the information on the rating plate.
4. The rated current on the rating plate will not be exceeded.
5. Make sure that no persons or objects are in the fan's hazardous area.
8.2
Procedure for commissioning
Sequence
Setting
1
If necessary, set the menu language in
Menu group
“
Start
”
.
(Default setting Swedish:
“
Språk S
”
)
2
Set the operating mode using the
Basic settings
menu group (default setting
4.02
=
Pressure regulation with
external temperature compensation
).
Attention!
When saving the operating mode, the respective preset factory operating-mode setting is loaded. That means,
the settings you have made, e.g., in
“
Motor Setup
”
are lost. An exception: the menu language setting remains
preserved.
8.3
Menu Mode
4.02
Start
Info
Setting
Events
Base
setup
Controller
Setup
IO Setup
Limits
Motor
Setup
Diagnostic
- - - - -
PIN input
0.0 Pa
E1 Actual
100.0 Pa
Setpoint1
-0-
Motor fault
4.02
Mode
OFF
PIN Protec-
tion
|
1A
|
A Function
OFF
Level.
Function
20 sec
Rampup
time
OTC
00012:56:-
15
GB Lan-
guage
23.9
°
C
E2 Actual
- - - - -
Setpoint2
-1-
External
error
200 DSG
E1 Analog
In
OFF
Set protec-
tion
0.0 V
A min.
- - - - -
Level min
20 sec
Rampdown
time
OTM
00010:56:-
11
OFF
Reset
100.0 Pa
Setpoint1
100.0 Pa
Pband
-2-
Sensor 2
- - - - -
E1 Deci-
mals
OFF
Save User
Setup
10.0 V
A max.
- - - - -
Level max.
15 %
Startvolt-
age
43.0
°
C
E1-KTY
4.02
Mode
100.0 Pa
Setpoint
control
0 %
Min. Speed
- - - - -
E1 Unit
- - OFF
Alarm sen-
sors
OFF
A Inverting
- - - - -
Level Delay
OFF
Suppres-
sion
1.14
Acontrol
100 %
Modulation
100 %
Max.
Speed
0.0 Pa
E1 Offset
- - - - -
Limit
OFF
D1 Func-
tion
OFF
Lmt E1
Function
6E
E2 Func-
tion
OFF
Msco
- - - - -
D1 Invert-
ing
- - - - -
Lmt E1 min
Operating Instructions
REPT6 / REPT10
Start-up
L-BAL-E081-GB 1237 Index 002
Part.-No. 00163316-GB