7.2
Select operation mode
Information
Simple installation is possible through the selection of the preprogrammed mode of operation.
This determines the basic function of the device.
The controller con
fi
guration is carried out automatically when selecting the application-specif-
ic operating modes. The factory defaults for each operating mode are based on many years of
experience and represent values suitable for a wide range of applications. In exceptional
cases, these can be adjusted individually (
Controller setup:
“
Controller con
fi
guration
”
).
The purpose of the device is to reach and maintain the target values set. To accomplish this, the
measured actual value (sensor value) is compared with the adjusted target value, and the controlled
value (modulation) is deduced from this.
Mode
Signal or Sensor
(input)
Function
1.01
Signal 0 - 10 V
Speed controller, two step operation (factory setting)
2.01
Sensor TF..(E1)
Temperature control airconditioning and refrigeration.
(preset set-point 20.0
°
C, P-band 5 K)
2.02
Sensor TF..(E2)
Temperature control depending on outdoor temperature
(preset set-point 5.0
°
C, - P-band 20 K)
2.03
Sensor TF..(E1)
Temperature control with additional functions (shutter and heat-
ing)
2.04
1x Sensor TF..(E1)
1x Sensor TF..(E2)
Temperature control with two sensors, comparison or average
2.05
1x Sensor TF..(E1)
1x Sensor TF..(E2)
Temperature control with two sensors differential temperature
3.01
Sensor MBG.. (E1)
Pressure control condensers (refrigeration)
3.02
Sensor MBG..(E1)
Pressure control for condensers with input for refrigerant
3.03
1x Sensor MBG..(E1)
1x Sensor MBG..(E2)
Pressure control for two circuit condensers
3.04
1x Sensor MBG..(E1)
1x Sensor MBG..(E2)
Pressure control for two circuit condensers with input for refrig-
erant
4.01
Sensor DSG..(E1)
Pressure control for ventilation systems
4.02
1x Sensor DSG..(E1)
1x Sensor TF..(E2)
Pressure control depending on outdoor temperature
Default settings as delivered
4.03
1x Sensor DSG..(E1)
1x BUS RS 485
Pressure control depending on outdoor temperature, MODBUS
for outdoor temperature and remote control by central operating
device type AXE-200
5.01
Sensor DSG..(E1)
Volume control (constant) for ventilation systems
5.02
1x Sensor DSG..(E1)
1x Sensor TF..(E2)
Volume control with setpoint depending on outdoor temperature
6.01
Sensor MAL..(E1)
Air velocity control e.g. clean room
Information
The devices described in these instructions are supplied with a default setting of
4.02
(pressure
regulation with external temperature compensation) and a menu language of Swedish. The Save
basic user settings
“
PIN9091
”
or
“
Save user setup
”
function is used for this purpose.
When
“
PIN9095
”
is entered, the device is reset to the factory defaults, with operating mode
1.01
and English as the menu language!
Operating Instructions
REPT6 / REPT10
Base setup
L-BAL-E081-GB 1237 Index 002
Part.-No. 00163316-GB