By entering
“
PIN 9095
”
in the
“
PIN
”
menu in the
“
start
”
menu-group, the device is entirely
reset to the pre-delivery condition.
Any changes that have been made to the settings are thus lost!
9.8.5
Sensor Alarm ON / OFF
Function only in controller mode (
2.01
)!
For
“
E1 Analog In
”
and if activated for sensor 2
“
E2 Analog In
”
.
In case of an interruption or short-circuit in the sensor conductor, or in case of measured values that
lie outside of the device
’
s measurement range, a time-delayed fault indication takes place.
Alarm sensors
With
“
Alarm Sensors
”
=
“
OFF
”
(factory setting). Indicated
sensor disturbances are displayed as
“
Message
”
alternating
to the actual value and stored in the menu of
“
Events
”
.
Sensor 1
Alarm sensors
With
“
AlarmSensors
”
=
“
ON
”
areindicated sensor disturban-
ces as
“
Alarm
”
alternating to the actual value and stored in
the menu of
“
Events
”
.
Indication via relays is possible (
IO Setup / function relay
outputs).
Sensor 1
9.8.6
Limit
Limit
After allocation of a digital input (
IO Setup) an adjustable limitation of the modulation
can be activated via a digital input (
“
D1
”
,
“
D2
”
, ..).
As long as no allocation has been carried out
“
IO Setup
”
. Display:
|
- - - -
|
“
Limit value
”
= max. possible modulation (e.g.
speed reduction during night operation by
time switch).
Setting range:
“
Limit
”
=
“
n-max
”
up to
“
n-min
”
.
Factory setting: 100 %
max. modulation, i.
e. no limit.
Setting depending on device tye in: % or rpm.
n Motore
50 %
100 %
Regolatore P:
Min.
Limite 70% Min. 0 % Max. = 100 %
50 %
0 %
100 %
Limite
Limite 70% Min. 35 % Max. = 85 %
29.03.2007
v_limit.vsd
Valore
nominale
Campo di regolazione
Regolatore di velocità:
Segnale di impostazione
Scostamento di regolazione
Limit (idealized principle diagram)
nM
Motor speed
L
Limit
S
Setpoint
R
Pband
D
Speed controller: setting signal
P
P-controller: control deviation
9.8.7
Minimum speed cut off
Min. speed cut off
This function is primarily signi
fi
cant for installation of the device as a pure P Controller
in refrigeration and air-conditioning technology.
For operation mode speed controller
1.01
without function!
Operating Instructions
REPT6 / REPT10
Programming
L-BAL-E081-GB 1237 Index 002
Part.-No. 00163316-GB