9.3.3
Menu for pressure control airconditioning
4.01
...
4.03
Parameter
Factory setting
User Setting
Start
PIN input
- - - - -
- - - - -
- - - - -
Language
GB
GB
GB
Reset
OFF
OFF
OFF
Mode
4.01
4.02
4.03
Acontrol
1.14
1.14
1.14
Info
E1 Actual
88.7 Pa 88.7 Pa 88.7 Pa
E2 Actual
- - - - -
21.0
°
C 21.0
°
C
Setpoint1
100 Pa
100 Pa
100 Pa
Setpoint control
100 Pa
100 Pa
Modulation
0 %
0 %
0 %
Msco
OFF
OFF
OFF
Setting
Setpoint1
100 Pa
100 Pa
100 Pa
4.01
Pressure control for ventilation systems
Setpoint2
- - - - -
- - - - -
100 Pa
Pband
100 Pa
100 Pa
100 Pa
Min. Speed
0 %
0 %
0 %
Max. Speed
100 %
100 %
100 %
4.02
Pressure control depending on outdoor temperature
Manual mode
OFF
OFF
OFF
Speed man.
100 %
100 %
100 %
T-Band SA
30.0 K
30.0 K
T-Start SA
15.0
°
C
15.0
°
C
P-Min SA
70.0 Pa
70.0 Pa
4.03
Pressure control depending on outdoor temperature,
Modbus for outdoor temperature and remote control
by central operating device type AXE-200
Events
Base setup
Mode
4.01
4.02
4.03
E1 Analog In
DSG200 DSG200 DSG200
E2 Function
E1 Min.
- - - - -
- - - - -
- - - - -
|
1E
|
external Setpoint
E1 Max.
- - - - -
- - - - -
- - - - -
E1 Decimals
- - - - -
- - - - -
- - - - -
|
2E
|
external manual mode
E1 Unit
- - - - -
- - - - -
- - - - -
E1 Offset
0.0 Pa
0.0 Pa
0.0 Pa
|
3E
|
Sensor average to E1
E2 Function
OFF
6E
6E
E2 Analog In
- - - - -
TF
Bus
|
4E
|
Sensor comparison to E1
E2 Min.
- - - - -
- - - - -
-35.0
°
C
E2 Max.
- - - - -
- - - - -
65.0
°
C
|
5E
|
Sensor difference to E1
E2 Decimals
- - - - -
- - - - -
- - - - -
E2 Unit
- - - - -
- - - - -
°
C
|
6E
|
Sensor for Setpoint
E2 Offset
- - - - -
0.0 K
0.0 K
Further menus see chapters:
•
Controller Setup
•
IO Setup
•
Limits
•
Motor Setup
•
Diagnostic
|
7E
|
Measurement
Operating Instructions
REPT6 / REPT10
Programming
L-BAL-E081-GB 1237 Index 002
Part.-No. 00163316-GB
32/67