Manual - TC.P Quadro
6) Communication
2016-08-05
283/330
V04.52
9
Flash
Code
Error
Error message
TopCon (Long)
Description
Possible Cause
Counteraction
7-4
63
CAN transmission
aborted
Internal conflict between DSP and
CAN-Controller.
In case of repeated occurrence
refer to customer support
In case of repeated occurrence refer to customer
support
7-5
64
CAN receive mes-
sage lost
Internal conflict between DSP and
CAN-Controller.
In case of repeated occurrence
refer to customer support
In case of repeated occurrence refer to customer
support
7-6
65
HMI/RCU does not
respond
The device with master role gets no
response from interface unit HMI or
RCU.
Supply voltage for a correspond-
ing HMI / RCU too low.
Check RCU supply voltage.
7-6
65
HMI/RCU does not
respond
The device with master role gets no
response from interface unit HMI or
RCU.
Communication interruptions.
Cf. 60) and 61)
7-7
66
CAN transmit
queue overrun
Internal conflict between DSP and
CAN-Controller.
Subsequent error from error
60/61):
No CAN bus participant receives
data. Or (if no subsequent error):
Internal Problem
In the case of repeated occurrence refer to cus-
tomer support (if no subsequent error).
7-8
67
Slave does not
respond
The master does not receive data
from all connected devices.
Communication interruptions.
Cf. 60) and 61)
7-8
67
Slave does not
respond
The master does not receive data
from all connected devices.
Slave was switched off
Check the mains supply of slaves.
7-9
68
RMB not connected
Optional external measuring box
(RMB) is not connected
Supply voltage of RMB too low.
Check supply voltage.
7-9
68
RMB not connected
Optional external measuring box
(RMB) is not connected
Optical fibre is not correctly con-
nected.
Check the correct mounting of the optical fibre
cable.
7-10
69
Slave does not get
data from master
A slave does not get data from mas-
ter
The master is switched off.
Check the mains supply of master
7-10
69
Slave does not get
data from master
A slave does not get data from mas-
ter
Communication error.
Cf. 60) and 61)
7-10
69
Slave does not get
data from master
A slave does not get data from mas-
ter
Error caused by a failed login or a
wrong system configuration.
Cf. group errors C) and D) (if applicable note error
messages of master device).
7-11
6A
TC.LIN does not
respond
between TC.LIN and TopCon (after a
previously successful communica-
tion). TC.LIN ceased sending data.
Communication error.
Reattach cable,
acknowledging the error via master,
device restart system.