Manual - TC.P Quadro
HMI and RCU
2016-08-05
165/330
V04.52
6
VLS settings
– page 1
Fig. 95
VLS settings page 1
– DISPLAY 24
VLS settings page 1
– DISPLAY 24
1
Input,
menu item
Selection of the actual value
s to which the VLS function reacts:
VLS disabled:
The VLS function is disabled.
DISPLAY 5 and DISPLAY 6 cannot be seen on the DIS-
PLAY.
voltage:
VLS reacts to the actual value for the output voltage.
current:
VLS reacts to the actual value for the output current.
power:
VLS reacts to the actual value for the output power.
2
Function,
menu item
Selection of the thresholds from
-1-
at which the VLS function reacts:
upper limit:
VLS reacts to an upper signal threshold.
lower limit:
VLS reacts to a lower signal threshold.
inside window:
VLS reacts to signals within
threshold window.
outside window:
VLS reacts to signals that are outside
a threshold window.
3
Action,
menu item
How the switching relay defined in -4- is to be react:
open relais:
The relay is to open
when the state set in -2- occurs.
close relais:
The relay is to close
when the state set in -2- occurs.
4
Output,
menu item
Which relay is to be operated with VLS.
warn relais, run relais, OK/alarm relais
.
5
VLS page 2 ... ,
navigation item
Continue to page 2 of the VLS settings
– DISPLAY32
Table 89
VLS settings page 1
– DISPLAY 24
VLS settings
page 1
Input
Function
Action
Output
VLS disabled
upper limit
close relais
warn relais
VLS page 2 ...
VLS settings
page 1
Input
Function
Action
Output
VLS disabled
upper limit
close relais
warn relais
VLS page 2 ...
1
3
5
2
4