Manual - TC.P Quadro
Technical data
2016-08-05
35/330
V04.52
3
3.1.2.
Mains connection
Device type
TC.P.10
TC.P.16
TC.P.20 TC.P.32
Connection type
3 LPE (without neutral conductor)
Mains voltage
(3-phase, phase to phase)
400 V
eff
: 360 V
eff
– 440 V
eff
;
480 V
eff
: 440 V
eff
– 520 V
eff
for US
Mains frequency
48
– 62 Hz
Permissible mains imbal-
ance
< 3%
Connection rating
16 kVA
20 kVA
25 kVA
40 kVA
Current consumption
1
Model 400 VAC (3-phase)
20 A
eff
32 A
eff
40 A
eff
60 A
eff
Model 480 VAC (3-phase)
17 A
eff
27 A
eff
33 A
eff
50 A
eff
Inrush current
1
< 15 A
Nominal current
Circuit breaker
2
25 A
32 A
40 A
63 A
Breaking capacity
Circuit breaker
2
10 kA
Power factor (cos
φ)
> 0.85
– 0.87
Harmonics content
< 0.72
Efficiency approx.
90 %
92 %
93 %
95 %
Power loss
approx.
1.1 kW
1.4 kW
1.5 kW
2.0 kW
Table 15
Electrical parameters for the various TopCon power classes.
1
At nominal voltage on the mains connection.
2
Built-in circuit breaker.
Leakage current
Leakage current AC
230 V
AC
; 50 Hz
Approx. 22 mA
Leakage current DC
1500 V
DC
< 1 mA
Table 16
Leakage current.