Manual - TC.P Quadro
E) Configuration 2
2016-08-05
304/330
V04.52
9
9.1.15.
E) Configuration 2
Flash
Code
Error
Error message
TopCon (Long)
Description
Possible Cause
Counteraction
15-1
E0
No ReGen stand-
ard config specified
Internal parameter for operating a
ReGen system has not been set.
Internal parameter for operating a
ReGen system has not been set.
Contact customer support to parameterise the
corresponding set value.
15-2
E1
TC.LIN not enabled
On TopCon master device TC.LIN
was not set active but at power-up a
TC.LIN was found.
Operating with TC.LIN favoured.
Use TopControl (version > 4.11.63) connected to
Top-
Con master to activate flag “TC.LIN enabled”
(system configuration).
15-2
E1
TC.LIN not enabled
On TopCon master device TC.LIN
was not set active but at power-up a
TC.LIN was found.
Operating without TC.LIN fa-
voured
Switch off the TC.LIN device or disconnect it from
system.
15-3
E2
Nominal voltage of
a TC.LIN not con-
sistent
The nominal voltage of a TC.LIN
doesn’t match the system voltage of
the TopCon system.
The proposed voltage of one
TC.LIN device at minimum doesn’t
match to the system voltage of the
TopCon system.
Use different TC.LIN or TopCon system.
15-4
E3
Invalid PLD version
Version of internal PLD does not
match
Contact customer support
15-5
E4
Invalid IBC version
Version of internal IBC board does
not match
Contact customer support
15-6
E5
Not all Slaves in
series connection
are capable of Q4
All Slaves in series connection must
be of the same type (GSS or not)
Only connect all GSS or all Non-GSS Slaves in
series
15-7
E6
RSC: Invalid Modu-
leID or ModuleAd-
dress
RSC: Wrong module ID or module
address
Wrong Configuration-file or wrong
module ID setting on slave
Check the modul ID's on the slaves.
Contact customer support
15-8
E7
RSC: Invalid Com-
munication to
switchbox
RSC: Choosed wrong communica-
tion to switch box
Contact customer support
15-9
E8
RSC: Wrong con-
figuration number
for switch box
RSC: Wrong configuration number
for the switch box
Wrong Configuration-file or wrong
default value of maximum configu-
rations
Contact customer support
15-10 E9
RSC: Wrong swit-
chboxID
RSC: Wrong switchboxID in system
SwitchboxID is 0.
Contact customer support