Appendix A: Troubleshooting
73
Problem
Possible causes
Possible solutions
Temperature does not change
There are no working temperature
probes enabled or connected
Make sure at least one working probe is
enabled. For more information, read
Unusually high or low
temperature readings
A non-Phason probe is connected
to TEMP 1/2/3/4
Remove the probe and then install a Phason
probe.
The extension cable connected to
the temperature probe is providing
a poor connection
Check the extension cable connection.
Resolder it if necessary.
Damaged probe
Replace the temperature probe.
Variable fan runs at maximum
Incorrect wiring
Correct the wiring. For more information,
read
Connecting variable heating or
The minimum idle speed is too
high.
Decrease the minimum idle speed setting.
The on full at setting is the same
as the temperature set point.
Adjust the temperature set point to the
desired temperature. For more information,
read
Programming variable cooling stages
Incorrect motor curve
Configure the stage to use the other motor
curve. For more information, read
Variable fan not running
Incorrect wiring
Correct the wiring. For more information,
read
Connecting variable heating or
The fuse is open or blown.
Check why the fuse was blown and then
repair any problems. Replace the fuse.
The variable stage is configured
as OFF
Configure the variable stage for cooling. For
The idle speed setting is too low.
Increase the idle speed setting. For more
on page 49. See also
Programming minimum ventilation curves
The off at temperature setting is
too high.
Decrease the off at temperature setting. For
The temperature set point is
above room temperature.
Adjust the temperature set point to the
desired temperature. For more information,
read
Programming variable cooling stages
There is no power to the fan.
Switch on the power.
Faulty fan/heater
Replace the equipment.