Programming zone settings
45
7.
Press the
Up
or
Down
arrows below
Starting Output
to set the output at the beginning of the
influence range, and
Ending Output
to set the output at the end of the influence range.
8.
When finished, press
Save
.
To remove modifiers
1.
Press the
Menu
and then
Settings
.
2.
Press
Modifiers
.
3.
Press the
Left
or
Right
arrows beside
Output
and
Modifier
to choose the output and modifier you
want to remove.
4.
Press
Clear Modifier
.
5.
Press
Save
.
Programming alarms
An alarm occurs if an enabled alarm condition is present for longer than the minimum duration of
one minute. The one minute minimum duration prevents alarms from occurring when the
temperature rises or drops for just a few seconds. The exception to the one minute minimum is
actuator jam alarms. Actuator jam alarms activate 20 seconds after the alarm is detected.
When an alarm occurs, the alarm relay triggers (switches) and a message flashes on the screen. For
more information, read
The actuator jam alarm has no settings, which you can enable or disable it. Temperature alarms are
described below.
Temperature alarms
If the high temperature alarm setting is 85.0°F and the temperature rises to 86 degrees, but drops
below 85 degrees 30 seconds later (before the minimum duration of 1 minute), there is no alarm.
If the temperature rises to 86 degrees and stays there for 1 minute, an alarm occurs. The alarm relay
remains active until the temperature drops below the high temperature alarm setting.
Outdoor temperature compensation
The purpose of outdoor temperature compensation is to prevent high temperature alarms from
occurring on hot days when the temperature set point cannot be maintained. Outdoor temperature
compensation is available for zones only, not individual sensors, and requires a temperature sensor
that is mounted outdoors.
Outdoor compensation is the offset added to the high temperature alarm setting when the outdoor
temperature is higher than the high alarm setting. High maximum is the highest temperature you can
have in the zone; any temperature above this value is an alarm condition.