What you need to know before installing the Plus Touch
11
Electrical ratings
Input power
120/230 VAC, 50/60 Hz
Variable stages
(2: VARI-1, VARI-2)
Fuses
(2: F1and F2)
10 A at 120/230 VAC, general-purpose (resistive)
7 FLA at 120/230 VAC, PSC motor
1/2 HP at 120 VAC, 1 HP at 230 VAC, PSC motor
15 A, 250 VAC ABC-type ceramic
Relay stages
(6: STG-1 to STG-6)
10 A at 120/230 VAC, general-purpose (resistive)
1/3 HP at 120 VAC, 1/2 HP at 230 VAC
360 W tungsten at 120 VAC
Alarm relay
0.4 A at 125 VAC; 2 A at 30 VDC, resistive load
0.2 A at 125 VAC; 1 A at 30 VDC, inductive load
You can connect more than one piece of equipment to a variable stage or relay as long as they are the same type (for
example, two fans) and the total current draw does not exceed the stage’s limit.
The FLA (full load ampere) rating accounts for the increase in motor current draw
when the motor operates at less than full speed. Make sure the motor/equipment
connected to the variable stage does not draw more than 7 FLA.
Using power contactors to increase the capacity of relays
Phason’s Manual Override Box (
model MOB-4
) has four 240-volt power contactors that allow you to
increase the load handling capability of control relays. Manual Override Box is ideal for secondary
ventilation fans and electric heaters.
MOB-4 electrical ratings
Coil:
10.2 mA at 240 VAC
Contact: 25 A at 240 VAC; resistive
2 HP at 240 VAC, 1 HP at 120 VAC; motor, power factor 0.4
1300 W at 120 VAC; tungsten
For more information, read