Testing sensors and equipment
63
Acknowledging alarms
An alarm occurs if an enabled alarm condition is present for longer than the minimum duration of
one minute. The one minute minimum duration prevents alarms from occurring when the
temperature rises or falls or just a few seconds. The exceptions to the one minute minimum are the
actuator jam alarms. Actuator jam alarms activate 20 seconds after the alarm is detected.
When an alarm occurs, the alarm relay triggers (switches) and a message flashes on the screen.
To acknowledge alarms
Press
Dismiss
to silence the alarm, or
Go to Alarms
to silence and then go to alarm settings.
Acknowledging alarms clears the alarm message; it does not deactivate the
alarm relay. To deactivate the alarm relay, resolve the problem causing the
alarm condition.
If you acknowledge the alarm, but do not resolve the problem causing the
alarm condition, the alarm message displays again after the alarm silencing
duration. For more information, read
Testing sensors and equipment
Using manual override
Manual override allows you to override one or more sensors or pieces of equipment. Manual
override is useful for testing equipment and settings, or for diagnosing problems.
For variables, you can adjust the output.
For relays and curtains, the state
For actuators, the position
For sensors, the sensor reading.
To override sensors or equipment
Option 1 - single sensor or piece of equipment
1.
If you are on any screen other than the Status screen, press the
Home
button.
2.
Press the
Left
or
Right
arrows to select sensor or equipment you want to override.
3.
Press the widget button (the colored button in the center of the screen).