Programming zone settings
41
To program growth curves
1.
Press the
Menu
and then
Settings
.
2.
Press
Staged Ventilation
.
3.
Press
Ventilation Curve
.
4.
Below
Zone
, press the
Left
or
Right
arrow to choose the zone.
5.
Below
Step Start Day
, press the
Up
or
Down
arrows to set the start day for each step.
6.
Below
Restart Day
, press the
Left
or
Right
arrow to choose the zone.
7.
Below
Temperature
, press the
Up
or
Down
arrows to set the master set point for the start day of
each step.
8.
When finished, press
Save
.
To change the current day
1.
Press the
Menu
and then
Settings
.
2.
Press
Staged Ventilation
.
3.
Press
Ventilation Curve
.
4.
Below
Current Day
, press the
Left
or
Right
arrow to change the day.
5.
When finished, press
Save
.
Programming minimum ventilation curves
Minimum ventilation is very important for controlling humidity and getting rid of gases such as
carbon dioxide and ammonia. Insufficient ventilation can cause high humidity, high gas levels, and
stagnant air. As animals grow older, they require more fresh air but produce more humidity and
gases. Using a minimum ventilation curve, you can have Plus Touch automatically adjust the
minimum ventilation as the animals grow.
The minimum ventilation curve affects only the first variable stage that is
configured as cooling for the zone.
If you are using a minimum ventilation curve you cannot adjust the idle speed
in the variable stage settings.
How ventilation curves work
Plus Touch reads the curve each day at midnight changes the idle speed setting for the current day.
At the end of the curve, the control continues using the settings from the last day of the curve.