Programming zone settings
43
To change the current day
1.
Press the
Menu
and then
Settings
.
2.
Press
Staged Ventilation
.
3.
Press
Ventilation Curve
.
4.
Below
Current Day
, press the
Left
or
Right
arrow to change the day.
5.
When finished, press
Save
.
Programming modifiers
Modifiers, sometimes called influencers, allow you to override equipment settings when certain
conditions are met, regardless of temperature. You can have up to three modifiers for each variable
stage or relay.
Type and sensor
Type can be either a zone reading or sensor reading. Zone reading is the average temperature of all
temperature sensors configured for the zone. If you have other sensors configured as modifiers for
the zone, for example CO2 (carbon dioxide) or NH3 (ammonia), you can choose one of those types.
If you select a type of sensor and there is more than one sensor of that type, you need to select the
specific sensor you want to use.
You must have a sensor configured to modify equipment settings in the zone
before you can select it as a modifying sensor. For more information, read
Modifier modes
Set value modifiers
set a variable stage or relay to a specific value or state when a condition is met.
For example, “When the humidity is over 90%, switch on a fan.”
Influence modifiers (variable only)
adjust the output of a variable
stage proportionally over a range of values. The adjustment can
be an increase or decrease.
For example, let's say a CO
2
modifier starts at 2500 ppm and
ends at 3500 ppm; the starting adjustment is +10 and ending is
+40. When the CO
2
is 2500, the modifier increases the output
by 10%. As the CO
2
rises, the modifier increases in the output
proportionally until the CO
2
is 3500 ppm and the 40%.