Connecting equipment to the Plus Touch
21
Connecting Phason 3K temperature sensors
Plus Touch has four zone-temperature sensor terminals, TEMP1 to TEMP4. You can connect any
of Phason’s standard 3K temperature sensors to these terminals. All connected and enabled probes
are averaged to provide a more balanced temperature reading in the zone.
You can also connect a Phason 3K temperature sensor to the OUTDOOR terminal for monitoring
outdoor temperatures.
If there are no functioning temperature sensors, Plus Touch controls the
equipment as if the master set point for the zone is the actual temperature.
Replace damaged temperature sensors as soon as possible. If a temperature
sensor is damaged, disable it until you can replace it with a new one.
When routing the temperature probe cables, do not run them in or along the
same conduit as AC-power lines.
You can extend probe cables up to 500 feet. For more information, read the
Control Fundamentals
guide that came with your control.
To connect temperature sensors
Follow these guidelines and connect the temperature sensor as
shown below.
Do not run the sensor cable in the same conduit as AC
power cables
Do not run the sensor cable beside AC power cables or near
electrical equipment.
When crossing other cables or power lines, cross them at a
90-degree angle.