Programming equipment settings
51
To program variable stages for ventilation
1.
Press the
Menu
and then
Settings
.
2.
Press
Staged Ventilation
.
3.
Press
Variable Stages
4.
Press stage you want to program.
5.
Press the
Up
or
Down
arrows to each of the settings.
6.
When finished, press
Save
.
Programming variable heating stages
Before setting up the variable stages, make sure you have properly configured them. For more
information, read
How variable heating stages work
When the temperature is above the
heat cutoff
temperature, the heater is off.
When the temperature drops below the
heat cutoff
temperature, the heater is at the
minimum
heat
. The heater operates at
minimum heat
until the temperature drops to the
set point
.
When the temperature is between the
set point
and the
differential
temperatures, heater output
increases or decreases proportionally with the temperature.
When the temperature is below the
differential
temperature, the heater is at full output.