112
17. Heating or cooling module
Error codes
When the module is functioning properly, the STATUS LED will light up in TEST mode only. If one or several errors occur,
the LED will blink to indicate the error code of the error with the highest priority. The table below provides an overview of
all error codes.
Technical data
• maximum current per module: 16 A
• connection terminals to control 4 valves at 230 Vac or 24 Vdc, do not use both 230 Vac and 24 Vdc on the same
module
• connection terminals to control a central boiler or cooling unit
• connection terminals for 3 x 1.5 mm² or 2 x 2.5 mm² or 1 x 4 mm²
• dimensions: DIN 4U
• sliding contact
• CE marking
• ambient temperature: 0 - 45°C
The response time applies to all valves connected to the heating or cooling module. Choose similar valves for each
output.
Lag time of the central boiler or cooling unit.
What is this?
The time required by the central boiler or cooling unit to stop heating or cooling.
Why is this necessary?
To release residual heat or cold.
The control valve for the zone will remain open for the time selected to allow the
central boiler or cooling unit to release its residual heat or cold.
Standard setting
3 minutes
Details
If you are using electric heating units or individual cooling units, the lag time must
be zero.
If the central boiler or cooling unit is fitted with a circulation pump, the lag time
must be zero.
LED
ACTION
ERROR
POSSIBLE SOLUTIONS
STATUS LED
Blinks – one pulse per two
seconds.
Software error
Wrong software version.*
*Download the latest software version
from the Niko website to upgrade the
module.