7. Switching modules
51
Follow the steps below to install the module:
1
Press the switching module onto the DIN rail until it clicks into place.
2
Make a single-phase connection from the mains voltage to the L screw terminals.
The three-fold switching module has three independent L screw terminals, which means three power circuits can
be connected.
In the six-fold switching module, all six screw terminals at the bottom are looped into two groups of three, which
means two power circuits can be connected.
3
The switching circuits you wish to connect can now be connected to screw terminals 1’-3’ or 1’-6’.
4
Group all neutral conductors and connect these to an N screw terminal.
5
Connect the switching module to the module before it. Slide the sliding contact of this module to the right until it
clicks into the switching module. This will ensure that the bus and the power supply voltage are connected.
Error codes
When the module is functioning properly, the STATUS LED will light up in TEST mode only. If one or several errors occur,
the LED will blink to indicate the error code of the error with the highest priority. The table below provides an overview of
all error codes.
• Ensure that the installation is disconnected from the power mains when setting up the electrical cabinet.
• Observe all AREI regulations in force when connecting the load.
• Only one phase can be connected to each switching module.
• Use automatic fuses of 16 A max. for the switching module. Mount the fuses in front of the Niko Home
Control module.
• Verify whether each load corresponds to the specifications of the switching module. Do not connect loads
that are outside the permitted range directly to this module. The total load should not exceed 32 A-230 V for
a six-fold switching module and 40 A-230 V for a three-fold switching module.
LED
ACTION
ERROR
POSSIBLE SOLUTIONS
STATUS LED
Blinks – one pulse per two
seconds.
Software error
Wrong software version.*
*Download the latest software version
from the Niko website to upgrade the
module.