128
22. Analogue control module 1-10 V
Follow the steps below to install the module:
1
Press the module onto the DIN rail until it clicks into place. Preferably position the module in the top row inside the
electrical cabinet to keep the SELV cables separate from the 230 V cables.
2
Connect the dimmers to one of the screw terminals 1-3.
3
Connect the analogue control module 1-10 V to the module before it. Slide the sliding contact of this module to the
right until it clicks into the analogue control module 1-10 V. This will ensure that the bus and the power supply
voltage are connected.
Error codes
When the module is functioning properly, the STATUS LED will light up in TEST mode only. If one or several errors occur,
the LED will blink to indicate the error code of the error with the highest priority. The table below provides an overview of
all error codes.
Technical data
• 3 outputs: 1-10 V (FELV, functional extra-low voltage), current-controlled (I)
• option of connecting 3 individual phases
• maximum distance between dimmers and module: 50 m
• maximum load: 20 mA per channel, protected from 50 mA per channel and maximum 11 V
• galvanic isolation when connecting the power circuit (6 A per channel)
• connection terminals for 3 x 1,5 mm² or 2 x 2,5 mm² or 1 x 4 mm²
• dimensions: DIN 4U
• sliding contact
• ambient temperature: 0 - 45 °C
• CE marking
• Ensure that the installation is disconnected from the mains.
• The distance between the dimmers and the module should not exceed 50 m.
• A maximum of three dimmers can be connected per module.
It is possible to connect three individual phases.
LED
ACTION
ERROR
POSSIBLE SOLUTIONS
STATUS LED
Blinks – one pulse per two
seconds.
Software error
Wrong software version.*
*Download the latest software version
from the Niko website to upgrade the
module.