21. Analogue control module 0-10 V
125
Error codes
When the module is functioning properly, the STATUS LED will light up in TEST mode only. If one or several errors occur,
the LED will blink to indicate the error code of the error with the highest priority. The table below provides an overview of
all error codes.
Technical data
• 3 outputs: 0-10 V (FELV, functional extra-low voltage), voltage-controlled (U)
• maximum distance between dimmers and module: 50 m
• maximum load: 10 mA per channel
• short circuit protection per channel
• connection terminals for 3 x 1,5 mm² or 2 x 2,5 mm² or 1 x 4 mm²
• dimensions: DIN 2U
• sliding contact
• ambient temperature: 0 - 45 °C
• CE marking
LED
ACTION
ERROR
POSSIBLE SOLUTIONS
STATUS LED
Blinks – one pulse per two
seconds.
Software error
Wrong software version.*
*Download the latest software version
from the Niko website to upgrade the
module.