5. Wall-mounted printed circuit boards and push buttons
Installation
Connecting single wall-mounted printed circuit boards
The double plug-in connector is used for connecting the bus cable to the wall-mounted printed circuit board and for
establishing a connection to the next control element. It has two contacts with two openings each.
To connect single wall-mounted printed circuit boards, you connect the bus using two wires from the bus cable. Connect
each wire separately to one of the contacts. Each contact is marked by the letter B.
The wall-mounted printed circuit board is now connected. Use the other opening of the contact to establish a connection
to the next control element if required.
Connecting multiple wall-mounted printed circuit boards
You need one connection unit for each multiple wall-mounted printed circuit board you wish to connect. Connection units
are available separately. The connection unit includes a double plug-in connector, which allows you to connect the bus
cable and establish a connection to the next control element. The connector has two contacts with two openings each.
To connect multiple wall-mounted printed circuit boards:
1
Connect two wires of the bus cable to the contacts of the connection unit.
The connection unit is now connected. Use the other opening of the contact to establish a connection to the next
control element if required.
2
Remove the transparent tape from the wall-mounted printed circuit board where the connection unit will be
mounted. This connection unit is mounted closest to the flush-mounting box.
3
Press the connection unit onto the wall-mounted printed circuit board until it clicks into place. Secure the
connection unit using two screws.
550-14110
A.
Double plug-in connector
B.
Two contacts with two openings each
• Strip the wires of the bus cable 9 - 10 mm.
• A maximum of two wires with a diameter of 0.5 - 1 mm each can be connected per contact.
• Strip the wires of the bus cable 9 - 10 mm.
• A maximum of two wires with a diameter of 0.5 - 1 mm each can be connected per contact.
B
A
Содержание 550-00001
Страница 1: ...Installation Manual Niko Home Control...
Страница 17: ...16 3 Power supply Installation Connection diagram N L 230V...
Страница 65: ...64 9 Electricity measuring modules Measuring one or several switching circuits 230V L N 0 3 0 9 1 7 kWh L K...